| Plan Review Notes For Permit 07110373 |
| Permit Number |
07110373 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-19 16:10:39 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.THE APPLICATION STATES THAT THIS IS FOR WINDOW | | | REPLACEMENT, PLANS SHOW SLIDING GLASS DOORS. | | | | | | 2.PROVIDE THE CONDO ASSOCIATION APPROVAL. | | | | | | 3.THIS JOB IS IN EXPOSURE C, AND SOME OPENINGS APPEAR | | | TO BE IN ZONE 5.RATHER THAN HIGHLIGHT TWO ROWS OF | | | DESIGN PRESSURES, PLEASE EITHER CIRCLE ONE SET OF | | | NUMBERS TO APPLY TO THE ENTIRE JOB OR PROVIDE A | | | SCHEDULE SHOWING DESIGN PRESSURE PER OPENING.ON THE | | | PRODUCT APPROVAL, CIRCLE THE CONFIGURATION(S) YOU ARE | | | USING UNLESS YOU DESIGN THE ENTIRE JOB TO WORST CASE | | | DESIGN PRESSURE, WORST CASE PRODUCT DESIGN PRESSURE | | | LIMITATION.CODE COMPLIANCE MUST BE DETERMINED BASED | | | ON THE INFORMATION PROVIDED. | | | |
|