| Plan Review Notes For Permit 07110346 |
| Permit Number |
07110346 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-21 08:02:55 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | | | 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 | | | RESIDENTIAL FLORIDA BUILDING CODE. INDICATE COMPLIANCE | | | ON THE PLAN. | | | | | | 3} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED | | | WITH THE APPLICATION. SHOW WORK BEING DONE AND | | | COMPLIANCE WITH THE 2005 NEC IN THE AREA WHERE THE | | | KITCHEN IS TO BE REMOVED.106.1.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|