| 2007-12-10 08:00:17 | RESIDENTIAL ALTERATION BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE CLEAR DRAWINGS DRAWN TO SCALE AND SHOWING |
| | ALL SCOPE OF WORK IN DETAIL, INCLUDING DIMENSIONS AS |
| | REQUIRED BY SEC. 106.1.1 AND SEC. 106.1.3 OF CITY |
| | AMENDMENTS TO FBC 2004. PERSON RESPONSIBLE FOR THE |
| | DESIGN SHALL PROVIDE HIS/HERNAME AND SIGN DRAWINGS. |
| | |
| | 2- PROVIDE COMPLETEFRAMING DETAILS FORNEW FRENCH |
| | DOORS AS REQUIRED BY SEC. R301.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 3- PROVIDE NOTICE OF COMMENCEMENT AS REQUIRED BY SEC. |
| | 713.13 FLORIDA STATUTE. |
| | |
| | 4- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE WHEN |
| | CHANGINGUSE FROM GARAGE TO LIVING AREA. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 5- VALUATION STATEDIN THE PERMIT APPLICATION IS TOO |
| | LOW.UPDATE VALUATION TO INCLUDE ALL MATERIALS AND |
| | LABOR. OTHERWISE VALUATION WILL BE UPGRADED AS REQUIRED |
| | BY SEC. 108.3 OF CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) NEW FRENCH DOORS. |
| | |
| | B) ALL SIMPSON OR USP STRUCTURAL CONNECTORS |
| | SPECIFIED ON NEW DOOR FRAMING DETAILS. |
| | |
| | C) STORM SHUTTERS IF FRENCH DOORS DON'T HAVE IMPACT |
| | WINDOWS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | SEE ATTACHED SAMPLE. AND, CLEARLY IDENTIFY |
| | INSTALLATION TYPE (EG: WALL MOUNTED, ETC.) AND SPECIFIC |
| | ANCHOR TYPE AND SPACING TO BE USED. |
| | |
| | 7- PROVIDE SPECIFICATIONS IN PLANS SHOWINGTYPE OF |
| | WOOD TO BE USED IN ORDER TO COMPLY WITH SEC. R319.1(5) |
| | OF 2004 FLORIDA RESIDENTIAL CODE TO PROVIDE PROTECTION |
| | AGAINST WOOD DECAY. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |