| 2007-11-27 13:45:53 | RESIDENTIAL BUILDING REVIEW FIRSTCHECKLIST. REVIEW |
| | UNDER EXISTING BUILDING CODE 2004, FLORIDA RESIDENTIAL |
| | CODE 2004 AND FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED COMPLETE DRAWINGS/SPECSSHOWING COMPLIANCE |
| | WITH CHAPTER 10 OF 2004 FLORIDA RESIDENTIALCODE. |
| | PROVIDE ALL DIMENSIONS, CLEARANCES, CRICKET AND |
| | FIREBLOCKING INFORMATION. SEE CHAPTER 10 OF FLORIDA |
| | RESIDENTIALCODE AND PROVIDE ALL REQUIRED |
| | INFORMATION. |
| | |
| | 2- PROVIDE COMPLETE DESIGN CRITERIA AS REQUIRED BY SEC. |
| | R301OF 2004 FLORIDA RESIDENTIAL CODE. PLANS SUBMITTED |
| | DON'T PROVIDEDESIGN INFORMATION.SPECIFY BUILDING |
| | CODEUSED FOR DESIGN AND SPECIFY ALL LOADS, ALL |
| | DIMENSIONS,STRUCTURAL CONNECTORS, ETC.SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 3- PROVIDE PRODUCT APPROVALS FOR ALL SIMPSON OR USP |
| | STRUCTURAL CONNECTORS SPECIFIED IN ALL DETAILS AS |
| | REQUIRED BY DCA RULE 9B-72. PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND PAGE WHERE SPECIFIC |
| | CONNECTORS ARESHOWN. GO TO WWW.FLORIDABUILDING.ORG TO |
| | DOWNLOAD CORRESPONDING INFORMATION. |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALLPRODUCT APPROVALSAS |
| | REQUIRED BY SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | |
| | 5- PROVIDE NOTICE OF COMMENCEMENT AS REQUIRED BY SEC. |
| | 713.13 FLORIDA STATUTE. |
| | |
| | 6- PROVIDE PLANS DRAWN TO SCALE AS REQUIRED BY SEC. |
| | 106.1.3 CITY AMENDMENTS TO FBC 2004. ALSO,IDENTIFY |
| | PROJECT ADDRESS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |