2008-02-05 09:48:45 
  
  
 APPLICATION #07110219
 ELECTRICAL PLAN REVIEW
 218 ALMERIA ROAD
 2/5/08
 WEST PALM BEACH, FL.
  
 THESE ARE REPEAT COMMENTS FROM THE 11/29/07 REVIEW,
 THAT PREVIOUSLY WERE RESPONDED TO. NOW REAPPEAR WITH
 THE LAST RESUBMITTAL. SEE ASTERISK FOR FURTHER
 COMMENT.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225, 250 AND 230 CAN BE REVIEWED. *THE SITE
 PLAN SP1, INDICATES "125 AMPBOX", SHEET E3 INDICATES
 ALL PANELS ARE 100 AMP. CORRELATE THE DRAWINGS TO
 REFLECT THE PROPOSED EQUIPMENT , LABEL AND LOCATE
 SAME.
  
 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC. * THECALCULATION FOR
 THAT PANEL WERE NOT RESUBMITTED.WITH THE 1/10/08
 RESUBMITTAL.
  
 3} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL.
 106.3.5.4 FBC AS AMENDED.* THIS SCHEDULE WAS NOT
 RESUBMITTED.WITH THE 1/10/08 RESUBMITTAL
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.* THOSE SPECIFICATIONS HAVE BEEN SUBMITTED
 INDICATING A 18" SETBACK. THE NOTE ON SP1 INDICATES
 "GENERATOR 13" FROM HOUSE", WHICH IS WHAT GENERATED
 THIS COMMENT ORIGINALLY.
  
 6} THERE ARE REFERENCES TO "8/0 AND 12/0" CONDUCTORS ON
 THE RISER DIAGRAM. THESE ARE NOT LISTED AWG SIZES.* THE
 "8/0" GROUND APPEARS IN ALL FEEDS, SHEET E3.ALSO NOTE
 THE 3/0 FEEDERS, ALL PANELS, FOR A 100 AMP PANEL.
 INDICATE WHAT THE NOTE "1-1/4"C. #4GROUNDING ELECTRODE
 CONDUCTOR" IS IN REFERENCE TO, SITE ARTICLE TO
 REFERENCE HE INTENT OF THAT NOTE.
  
 7} THERE IS A "GROUNDING ELECTRODE CONDUCTOR" (250.66,
 SEE DEFINITION) IN THE FEED FROM THE TRANSFER SWITCH TO
 THE EM PANEL, AND ALL PANELS FED FROM THE MAIN. THIS
 SHOULD BE AN EQUIPMENT GROUNDING CONDUCTOR (250.122),
 AND SHOULD BE SIZED TO INDICATE COMPLIANCE. SEE
 PREVIOUS COMMENT, SAME CONDITION STILL EXISTS.
  
 PLEASE CHECK ALL DOCUMENTS ARE CORRECTED AND PRESENT IN
 THE PACKAGE THAT IS RESUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  