| | APPLICATION #07110219 |
| | ELECTRICAL PLAN REVIEW |
| | 218 ALMERIA ROAD |
| | 2/5/08 |
| | WEST PALM BEACH, FL. |
| | |
| | THESE ARE REPEAT COMMENTS FROM THE 11/29/07 REVIEW, |
| | THAT PREVIOUSLY WERE RESPONDED TO. NOW REAPPEAR WITH |
| | THE LAST RESUBMITTAL. SEE ASTERISK FOR FURTHER |
| | COMMENT. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON |
| | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, |
| | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225, 250 AND 230 CAN BE REVIEWED. *THE SITE |
| | PLAN SP1, INDICATES "125 AMPBOX", SHEET E3 INDICATES |
| | ALL PANELS ARE 100 AMP. CORRELATE THE DRAWINGS TO |
| | REFLECT THE PROPOSED EQUIPMENT , LABEL AND LOCATE |
| | SAME. |
| | |
| | 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO |
| | BE SERVED. 215.5. 702.5, 2005NEC. * THECALCULATION FOR |
| | THAT PANEL WERE NOT RESUBMITTED.WITH THE 1/10/08 |
| | RESUBMITTAL. |
| | |
| | 3} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL. |
| | 106.3.5.4 FBC AS AMENDED.* THIS SCHEDULE WAS NOT |
| | RESUBMITTED.WITH THE 1/10/08 RESUBMITTAL |
| | |
| | 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE |
| | GENERATOR INDICATING RECOMMENDED SETBACKS FROM |
| | STRUCTURES.* THOSE SPECIFICATIONS HAVE BEEN SUBMITTED |
| | INDICATING A 18" SETBACK. THE NOTE ON SP1 INDICATES |
| | "GENERATOR 13" FROM HOUSE", WHICH IS WHAT GENERATED |
| | THIS COMMENT ORIGINALLY. |
| | |
| | 6} THERE ARE REFERENCES TO "8/0 AND 12/0" CONDUCTORS ON |
| | THE RISER DIAGRAM. THESE ARE NOT LISTED AWG SIZES.* THE |
| | "8/0" GROUND APPEARS IN ALL FEEDS, SHEET E3.ALSO NOTE |
| | THE 3/0 FEEDERS, ALL PANELS, FOR A 100 AMP PANEL. |
| | INDICATE WHAT THE NOTE "1-1/4"C. #4GROUNDING ELECTRODE |
| | CONDUCTOR" IS IN REFERENCE TO, SITE ARTICLE TO |
| | REFERENCE HE INTENT OF THAT NOTE. |
| | |
| | 7} THERE IS A "GROUNDING ELECTRODE CONDUCTOR" (250.66, |
| | SEE DEFINITION) IN THE FEED FROM THE TRANSFER SWITCH TO |
| | THE EM PANEL, AND ALL PANELS FED FROM THE MAIN. THIS |
| | SHOULD BE AN EQUIPMENT GROUNDING CONDUCTOR (250.122), |
| | AND SHOULD BE SIZED TO INDICATE COMPLIANCE. SEE |
| | PREVIOUS COMMENT, SAME CONDITION STILL EXISTS. |
| | |
| | PLEASE CHECK ALL DOCUMENTS ARE CORRECTED AND PRESENT IN |
| | THE PACKAGE THAT IS RESUBMITTED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |