| 2008-01-14 14:45:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL |
| | REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | **PREVIOUS COMMENTS** |
| | |
| | 1. **OK** COMMENT ADDRESSED. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | 3. **OK** COMMENT ADDRESSED. |
| | |
| | 4. **NO** COMMENT NOTED HOWEVER. |
| | PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR INDICATING RECOMMENDED SETBACKS FROM |
| | STRUCTURES. |
| | |
| | **THERE WERE NO MANUFACTURER'S SPECIFICATIONS |
| | SUBMITTED FOR THE PROPOSED GENERATOR INDICATING |
| | RECOMMENDED SETBACKS FROM STRUCTURES. |
| | |
| | 5. **OK** COMMENT ADDRESSED. |
| | |
| | 6. **NO** COMMENT NOTED HOWEVER. |
| | NOTE: THERE IS AN OPEN GAS PERMIT #07020467 PRINTED FOR |
| | THIS ADDRESS FOR "GUARANTEED PLUMBING INC.". PLEASE |
| | CLARIFY WHY THE SUBMITTED GAS FOR THE GENERATOR WAS NOT |
| | SUBMITTED AS A REVISION TO THAT PERMIT. IS IT THE |
| | INTENT TO VOID OUT THAT PERMIT? PLEASE SUBMIT AN |
| | ORIGINAL NOTARIZED LETTER BY SAID CONTRACTOR INDICATING |
| | WHICH PERMIT IS TO BE VOIDED. |
| | |
| | **NOTE: UNTIL A NOTARIZED LETTER FROM SAID CONTRACTOR |
| | IS SUBMITTED INDICATING WHICH GAS PERMIT IS TO BE |
| | VOIDED THE GENERATOR PERMIT WILL NOT BE PRINTED. |
| | |
| | 7. **OK** COMMENT ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |