| 2007-11-29 13:23:32 | |
| | |
| | APPLICATION #07110219 |
| | ELECTRICAL PLAN REVIEW |
| | 218 ALMERIA ROAD |
| | 11/29/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON |
| | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, |
| | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225, 250 AND 230 CAN BE REVIEWED. |
| | |
| | 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO |
| | BE SERVED. 215.5. 702.5, 2005NEC |
| | |
| | 3} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL. |
| | 106.3.5.4 FBC AS AMENDED. |
| | |
| | 4} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH. |
| | |
| | 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE |
| | GENERATOR INDICATING RECOMMENDED SETBACKS FROM |
| | STRUCTURES. |
| | |
| | 6} THERE ARE REFERENCES TO ?8/0 AND 12/0? CONDUCTORS ON |
| | THE RISER DIAGRAM. THESE ARE NOT LISTED AWG SIZES. |
| | |
| | 7} THERE IS A ?GROUNDING ELECTRODE CONDUCTOR? (250.66, |
| | SEE DEFINITION) IN THE FEED FROM THE TRANSFER SWITCH TO |
| | THE EM PANEL, AND ALL PANELS FED FROM THE MAIN. THIS |
| | SHOULD BE AN EQUIPMENT GROUNDING CONDUCTOR (250.122), |
| | AND SHOULD BE SIZED TO INDICATE COMPLIANCE |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |