| 2008-06-16 10:17:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) 2) AS NOTED IN LAST TWO REVIEWS 11/15/07 AND 4/18/08 |
| | NOTE #2. PROVIDE FOR RETURN AIR FOR THE NEW LOFT, SEE |
| | 2004 FBC/R M1602.2. ENGINEERS RESPONSE WAS, THE STAIR |
| | TO THE LOFT IS OPEN AT THE CEILING ETC. PLEASE SEE THAT |
| | THE STAIR TO THE LOFT IS CLOSED OFF AT THE BOTTOM FROM |
| | THE RETURN AIR GRILL IN THE MASTER BEDROOM BY A WALL |
| | AND A DOOR SO RETURN AIR CAN NOT RETURN TO THE AIR |
| | HANDLER. PLEASE CORRECT. |
| | |
| | 2) MECHANICAL PLAN M1 NOW SHOWS 6"X6" METAL CURB |
| | (SLEEPERS) AND PLAN A5.0 DETAIL 19, SHOWS 8" METAL CURB |
| | (SLEEPERS). PER 2004 FBC TABLE 1509.7 CLEARANCE BELOW |
| | RAISED ROOF MOUNTED MECHANICAL UNITS. THE MINIMUM |
| | CLEARANCE ABOVE ROOF SURFACES IS 14" PLEASE CHECK THE |
| | TABLE AS THE UNIT YOU ARE INSTALLING MAY REQUIRE MORE |
| | CLEARANCE. SEE 2004 FBC/R M1301.1, FBC/M 306.5, AND |
| | FBC1509.7. PLEASE CORRECT. |
| | |
| | 3)AS NOTED IN LAST TWO REVIEWS 11/15/07 AND 4/18/08 |
| | NOTE #4. PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR |
| | PER-ENGINEERED A/C CONDENSER STANDS (IF USED), SEE FS |
| | 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC |
| | 9B-72.010(31)(G). |
| | |
| | 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR |
| | TIMES THE FEE. |
| | |
| | *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |
| | *** WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL |
| | (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS |
| | REQUIREMENT). |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |