2008-06-24 13:20:54BUILDING REVIEW APPROVED WITH PROVISO:
 1-VERIFY THAT 5'-0" SPIRAL STAIRS IS INSTALLED.
 2- SOIL TEST REPORT STATESSOILBEARING CAPACITY OF
 2,000PSF.ENGINEER OF RECORD REQUIRES 2,500 PSF SOIL
 BEARING CAPACITY. SEE FOUNDATION NOTES ON SHEET S-5.
 REVISE AS REQUIRED.
 3- PROVIDE COMPLETE PRODUCT APPROVAL FOR UNDERLAYMENT
 USED IN BALCONY ASSEMBLY.SEE SHEET A3.4.
 4- PROVIDE PRODUCT APPROVAL FOR FLAT ROOF IF DOING ANY
 FLAT ROOF RE-ROOFING. SEE SHEET A2.2..
 5- REVISE ENERGY CALCULATIONS FOR GARAGE BUILDINGTO
 SHOWR-VALUE INSULATION ON WALLS AND CEILINGS. SEE
 ARCHITECTURAL DRAWINGS.
 6- TRUSS PACKAGE TO HAVE NAME OF ENGINEER OF RECORD ON
 INDEX SHEET AS REQUIRED BYSEC. 61G15-31.003(5).