2008-04-18 10:49:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 11/15/07 NOTE #1. PLEASE
 SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS) SEE 2004 FBC 13-607.1.ABC.1. ONE SET OF
 THE ENERGY CALCULATIONS FOR THE CABANA HAS A ONE SHEET
 SUMMARY SHEET '?' SEE THE EXCEPTION TO 13-607.1.ABC.1.
  
 2) AS NOTED IN LAST REVIEW 11/15/07 NOTE #2. PROVIDE
 FOR RETURN AIR FOR THE NEW LOFT, SEE 2004 FBC/R
 M1602.2.
  
 3)AS NOTED IN LAST REVIEW 11/15/07 NOTE #3. PLAN M4
 CONDENSER UNIT ROOF DETAIL, SHOWS A 6'X6' P.T. SLEEPER.
 PER 2004 FBC/M 301.13 THE USE OF WOOD SLEEPERS SHALL
 NOT BE PERMITTED. PLEASE CORRECT.
  
 4)AS NOTED IN LAST REVIEW 11/15/07 NOTE #4. PLEASE
 SUBMIT PRODUCT APPROVAL OR AN NOA FOR PER-ENGINEERED
 A/C CONDENSER STANDS (IF USED), SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 5) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL
 (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS
 REQUIREMENT).
  
 **** UNDER 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A
 SUMMARY SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED
 BY THE ENGINEER AND HAS THE MINIMUM INFORMATION ON IT.
 **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING
 METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY
 BULB USED... **OUTDOOR WET BULB USED... **RELATIVE
 HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING
 REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN...
 **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)...
 **TOTAL COOLING REQUIRED WITH OUTSIDE AIR.
  
 MECHANICAL PLAN REVIEW BY;