| 2008-04-25 19:00:54 | RESIDENTIAL (R3) ADDITION AND ALTERATION, BUILDING |
| | REVIEW SECOND CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP |
| | TO AVOID EXPIRATION OF DOCUMENT. |
| | |
| | 2- NEED TO PROVIDE COPY OF IMPACT FEES PAID RECEIPT. |
| | (REPEAT COMMENT).ONLY PLANS WITH IMPACT FEES STAMP |
| | WAS SUBMITTED THIS TIME.NEED TO PROVIDE BOTH. |
| | |
| | 3-ACCORDING TOSPIRAL STAIRS INFORMATION SUBMITTED, |
| | ONLY 5'-0" DIAMETER STAIRS OR LARGER COMPLY WITH THE |
| | MINIMUM REQUIREMENTS.ARCHITECTURAL PLANS SHOW 4'-9" |
| | DIAMETER FOR STAIR OPENING. PLANS NEED TO BE REVISED AS |
| | REQUIRED TO ACCOMMODATEMIN. 5'-0" DIAMETER STAIRS. TO |
| | COMPLY WITH SEC. R311.5.8.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | SPECIFY TOTAL NUMBER OF RAISERS REQUIRED TO VERIFY |
| | COMPLIANCE WITH MAXIMUM RISER HEIGHT. |
| | |
| | 4- PROVIDE COMPLETE DETAILS/SPECS FOR ORNAMENTAL |
| | GUARDRAIL TO VERIFY COMPLIANCE WITH TABLE R301.5 AND |
| | SEC. R312.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | INFORMATION SUBMITTEDFROM RAILING WORKS IS ONLYFOR |
| | GENERALINFORMATION AND DOESN'T PROVIDEINFORMATION |
| | FOR ACTUAL PROPOSED ORNAMENTAL RAILING. |
| | |
| | 5- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) POLYFOAM USED FOR ROOF TILE. (REPEAT COMMENT). |
| | SEE ROOF TILE PRODUCT APPROVAL FOR LISTED POLYFOAM. |
| | |
| | B) FLAT ROOF: NEED TO SPECIFY WHICH APPROVED |
| | ASSEMBLY AND SPECIFIC FASTENING OPTION IS GOING TO BE |
| | USED. ALSO, NEED TO PROVIDE THE RAS 117 CALCULATIONS |
| | FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION #7.SEE GENERAL |
| | LIMITATIONS ON LAST PAGE OF NOA 07-0111.03 SUBMITTED. |
| | (REPEAT COMMENT). |
| | |
| | C) ARCHED DOORS AS SHOWN ON GARAGE EXTERIOR |
| | ELEVATIONS. (REPEAT COMMENT). |
| | |
| | D) DOUBLE HUNG WINDOWS.MARVIN WINDOWS AND DOORS |
| | FLORIDA PRODUCT APPROVAL FL4765-R0 IS MISSING THE |
| | DRAWINGS SHOWING THE WINDOWS.PROVIDE COMPLETE |
| | DRAWINGS. |
| | |
| | E) MULLIONS. CLEARLY MARK SPECIFIC MULLION SIZE AND |
| | ANCHORING TO BE USED TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | ***NOTE:THERE ARE PRODUCT APPROVALSFOR DOORS AND |
| | WINDOWS FROM PGT AND FROM MARVIN WINDOWS AND DOORS. |
| | PROVIDE ONLY THE PRODUCTAPPROVALFOR SPECIFIC |
| | PRODUCT THAT IS GOING TO BE INSTALLED.PGT OR MARVIN. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. SOME PRODUCT APPROVALS ARE |
| | MISSING THE ARCHITECT'S REVIEW STAMP. |
| | |
| | 7- PROVIDE COMPLETE SPECIFICATIONS FOR RAISED WOOD |
| | FLOOR IN GARAGE AREAAND RAISED WOOD FLOOR IN NEW |
| | ADDITION AREA TO SHOW COMPLIANCE WITH SECTIONS R319 |
| | (PROTECTION AGAINST DECAY)AND SEC. R408.1 THRU |
| | R408.3 OF 2004 FLORIDA RESIDENTIAL CODE (UNDER-FLOOR |
| | SPACE VENTILATION AND ACCESS).(REPEAT COMMENT). THERE |
| | ARE NO SPECS PROVIDED TO SHOW COMPLIANCE WITH SEC. |
| | R319. AND, LOCATION OF VENTILATION OPENINGSNEED TO BE |
| | BETWEEN 3' OF EACH CORNER AS REQUIRED BY SEC. R408.1. |
| | REVISEPLANS AS REQUIRED. |
| | |
| | 8- ENERGY CALCULATIONS: |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | B) COMPLETE INFORMATION ON TOP OF FORM. (REPEAT |
| | COMMENT). |
| | |
| | 9-SOIL TEST REPORT SHOWS SOIL BEARING CAPACITY OF |
| | 2000 PSF AND RECOMMENDS MINIMUM FOOTING WIDTH OF 24". |
| | STRUCTURAL PLANS REQUIRE 2500PSF SOIL BEARING CAPACITY |
| | AND FOOTING WIDTH IS LESS THAN THE ONE RECOMMENDED ON |
| | THE SOIL TEST REPORT.STRUCTURAL ENGINEER TO |
| | COORDINATEWITH GEO-TECHNICAL ENGINEER AND REVISE |
| | EITHER ONE THE SOIL TEST REPORT OR STRUCTURAL DRAWINGS |
| | AS REQUIRED. |
| | |
| | 10- SHEET A5.0:REVISE NAIL TYPETO BE USED FOR ROOF |
| | SHEATHING ON DETAIL #18.SEC. R803.2.3.1 REQUIRES MIN. |
| | 8D RING SHANK NAILS. REVISE AS REQUIRED. |
| | |
| | 11- SHEET A6: REVISE INSULATION SPECIFICATIONS ON ALL |
| | WALL ASSEMBLIES SHOWN ON THE WALL SCHEDULE. COORDINATE |
| | WITH THE ENERGY CALCULATIONS AND REVISE AS REQUIRED. |
| | (REPEAT COMMENT). |
| | |
| | 12- SHEET S-4:REVISE ALL INFORMATION ON DETAIL C |
| | REGARDING THE ROOF SHEATHING FASTENER TYPE AND SPACING. |
| | SEE SEC. R803.2.3.1 FOR MINIMUM TYPE OF NAIL AND |
| | SPACING REQUIRED INCLUDING ON ROOF ZONE #3. |
| | |
| | 13- TRUSS PACKAGE: |
| | A) ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE |
| | TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | B) TRUSS DRAWINGS NEED TO HAVE ENGINEER'S ORIGINAL |
| | SIGNATURE AS REQUIRED BY SEC. 61G15-23.002 FLORIDA |
| | STATUTE. AND CHAPTER 472 FLORIDA STATUTE. |
| | |
| | C) TRUSS COVER SHEET IS MISSING THE INFORMATION |
| | REGARDING THE ENGINEER OF RECORD. PROVIDE THIS |
| | INFORMATION. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |