2008-04-25 19:00:54RESIDENTIAL (R3) ADDITION AND ALTERATION, BUILDING
 REVIEW SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP
 TO AVOID EXPIRATION OF DOCUMENT.
  
 2- NEED TO PROVIDE COPY OF IMPACT FEES PAID RECEIPT.
 (REPEAT COMMENT).ONLY PLANS WITH IMPACT FEES STAMP
 WAS SUBMITTED THIS TIME.NEED TO PROVIDE BOTH.
  
 3-ACCORDING TOSPIRAL STAIRS INFORMATION SUBMITTED,
 ONLY 5'-0" DIAMETER STAIRS OR LARGER COMPLY WITH THE
 MINIMUM REQUIREMENTS.ARCHITECTURAL PLANS SHOW 4'-9"
 DIAMETER FOR STAIR OPENING. PLANS NEED TO BE REVISED AS
 REQUIRED TO ACCOMMODATEMIN. 5'-0" DIAMETER STAIRS. TO
 COMPLY WITH SEC. R311.5.8.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
 SPECIFY TOTAL NUMBER OF RAISERS REQUIRED TO VERIFY
 COMPLIANCE WITH MAXIMUM RISER HEIGHT.
  
 4- PROVIDE COMPLETE DETAILS/SPECS FOR ORNAMENTAL
 GUARDRAIL TO VERIFY COMPLIANCE WITH TABLE R301.5 AND
 SEC. R312.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 INFORMATION SUBMITTEDFROM RAILING WORKS IS ONLYFOR
 GENERALINFORMATION AND DOESN'T PROVIDEINFORMATION
 FOR ACTUAL PROPOSED ORNAMENTAL RAILING.
  
 5- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) POLYFOAM USED FOR ROOF TILE. (REPEAT COMMENT).
 SEE ROOF TILE PRODUCT APPROVAL FOR LISTED POLYFOAM.
  
 B) FLAT ROOF: NEED TO SPECIFY WHICH APPROVED
 ASSEMBLY AND SPECIFIC FASTENING OPTION IS GOING TO BE
 USED. ALSO, NEED TO PROVIDE THE RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7.SEE GENERAL
 LIMITATIONS ON LAST PAGE OF NOA 07-0111.03 SUBMITTED.
 (REPEAT COMMENT).
  
 C) ARCHED DOORS AS SHOWN ON GARAGE EXTERIOR
 ELEVATIONS. (REPEAT COMMENT).
  
 D) DOUBLE HUNG WINDOWS.MARVIN WINDOWS AND DOORS
 FLORIDA PRODUCT APPROVAL FL4765-R0 IS MISSING THE
 DRAWINGS SHOWING THE WINDOWS.PROVIDE COMPLETE
 DRAWINGS.
  
 E) MULLIONS. CLEARLY MARK SPECIFIC MULLION SIZE AND
 ANCHORING TO BE USED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 ***NOTE:THERE ARE PRODUCT APPROVALSFOR DOORS AND
 WINDOWS FROM PGT AND FROM MARVIN WINDOWS AND DOORS.
 PROVIDE ONLY THE PRODUCTAPPROVALFOR SPECIFIC
 PRODUCT THAT IS GOING TO BE INSTALLED.PGT OR MARVIN.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. SOME PRODUCT APPROVALS ARE
 MISSING THE ARCHITECT'S REVIEW STAMP.
  
 7- PROVIDE COMPLETE SPECIFICATIONS FOR RAISED WOOD
 FLOOR IN GARAGE AREAAND RAISED WOOD FLOOR IN NEW
 ADDITION AREA TO SHOW COMPLIANCE WITH SECTIONS R319
 (PROTECTION AGAINST DECAY)AND SEC. R408.1 THRU
 R408.3 OF 2004 FLORIDA RESIDENTIAL CODE (UNDER-FLOOR
 SPACE VENTILATION AND ACCESS).(REPEAT COMMENT). THERE
 ARE NO SPECS PROVIDED TO SHOW COMPLIANCE WITH SEC.
 R319. AND, LOCATION OF VENTILATION OPENINGSNEED TO BE
 BETWEEN 3' OF EACH CORNER AS REQUIRED BY SEC. R408.1.
 REVISEPLANS AS REQUIRED.
  
 8- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 B) COMPLETE INFORMATION ON TOP OF FORM. (REPEAT
 COMMENT).
  
 9-SOIL TEST REPORT SHOWS SOIL BEARING CAPACITY OF
 2000 PSF AND RECOMMENDS MINIMUM FOOTING WIDTH OF 24".
 STRUCTURAL PLANS REQUIRE 2500PSF SOIL BEARING CAPACITY
 AND FOOTING WIDTH IS LESS THAN THE ONE RECOMMENDED ON
 THE SOIL TEST REPORT.STRUCTURAL ENGINEER TO
 COORDINATEWITH GEO-TECHNICAL ENGINEER AND REVISE
 EITHER ONE THE SOIL TEST REPORT OR STRUCTURAL DRAWINGS
 AS REQUIRED.
  
 10- SHEET A5.0:REVISE NAIL TYPETO BE USED FOR ROOF
 SHEATHING ON DETAIL #18.SEC. R803.2.3.1 REQUIRES MIN.
 8D RING SHANK NAILS. REVISE AS REQUIRED.
  
 11- SHEET A6: REVISE INSULATION SPECIFICATIONS ON ALL
 WALL ASSEMBLIES SHOWN ON THE WALL SCHEDULE. COORDINATE
 WITH THE ENERGY CALCULATIONS AND REVISE AS REQUIRED.
 (REPEAT COMMENT).
  
 12- SHEET S-4:REVISE ALL INFORMATION ON DETAIL C
 REGARDING THE ROOF SHEATHING FASTENER TYPE AND SPACING.
 SEE SEC. R803.2.3.1 FOR MINIMUM TYPE OF NAIL AND
 SPACING REQUIRED INCLUDING ON ROOF ZONE #3.
  
 13- TRUSS PACKAGE:
 A) ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE
 TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 B) TRUSS DRAWINGS NEED TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE AS REQUIRED BY SEC. 61G15-23.002 FLORIDA
 STATUTE. AND CHAPTER 472 FLORIDA STATUTE.
  
 C) TRUSS COVER SHEET IS MISSING THE INFORMATION
 REGARDING THE ENGINEER OF RECORD. PROVIDE THIS
 INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712