Plan Review Notes
Plan Review Notes For Permit 07110196
Permit Number 07110196
Review Stop P
Sequence Number 1
Notes
Date Text
2007-11-27 15:05:25DENIED;
 1. CABANA SANITARY RISER DIAGRAM; THE SINK SHALL
 DISCHARGE DOWN STREAM OF THE BATHROOM GROUP. SEE FBC
 PLUMBING SECTION 909.1.
 2. 1ST FLOOR SANITARY RISER DIAGRAM; THE AUTOMATIC
 CLOTHES WASHER SHALL DISCHARGE INTO A 3"BRANCH DRAIN.
 SECTION 406.3.
 PLUMBING PLAN REVIEW BY;