Plan Review Notes
Plan Review Notes For Permit 07110196
Permit Number 07110196
Review Stop M
Sequence Number 1
Notes
Date Text
2007-11-15 14:50:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS) SEE 2004 FBC 13-607.1.ABC.1.
  
 2) PROVIDE FOR RETURN AIR FOR THE NEW LOFT, SEE 2004
 FBC/R M1602.2.
  
 3) PLAN M4 CONDENSER UNIT ROOF DETAIL, SHOWS A 6'X6'
 P.T. SLEEPER. PER 2004 FBC/M 301.13 THE USE OF WOOD
 SLEEPERS SHALL NOT BE PERMITTED. PLEASE CORRECT.
  
 4) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED A/C CONDENSER STANDS (IF USED), SEE FS
 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC
 9B-72.010(31)(G).
  
 *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL
 (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS
 REQUIREMENT).
  