| 2007-11-14 16:20:37 | |
| | |
| | APPLICATION #07110196 |
| | ELECTRICAL PLAN REVIEW |
| | 711 CLAREMORE DRIVE |
| | 11/14/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} REFERENCING THE RISER DIAGRAM FOR THE HOUSE SUBPANEL |
| | ON SHEET E3, THE FEEDER TO THAT PANEL MUST HAVE AN |
| | EQUIPMENT GROUND (#8 MINIMUM) PER 250.122. |
| | |
| | 2} THE HOUSE SUBPANEL CANNOT BE LOCATED IN THE BATHROOM |
| | AS INDICATED ON SHEET E1, 1ST FLOOR ELECTRICAL PLAN. |
| | SEE ARTICLE 240.24(E). |
| | |
| | 3} SHEET E2, THE RISER FOR THE CABANA INDICATES THAT |
| | SERVICE IS EXISTING, THE CABANA PANELBOARD INDICATES |
| | ?NEW?. CLARIFY IF NEW OR EXISTING, INDICATE THE |
| | GROUNDING ELECTRODE CONDUCTOR SIZE PER 250.66, MINIMUM |
| | #6. |
| | |
| | 4} THE 1? CONDUIT CONTAINING 3#1/0 CONDUCTORS FOR THE |
| | CABANA PANEL FEED IS IN VIOLATION OF THE CONDUIT FILL |
| | REQUIREMENTS. SEE ANNEX ?C? OR CALCULATE FROM TABLE |
| | #8. |
| | |
| | 5} THE CABANA PANEL LOCATION APPEARS NOT TO HAVE THE 3? |
| | CLEARANCE REQUIRED PER 110.26. PLEASE VERIFY. |
| | |
| | 6} THE LOAD CALCULATIONS ARE NOT PER 220.82 OR 220.83 |
| | AS THEY SHOULD BE FOR AN EXISTING RESIDENCE. THERE ARE |
| | LOADS ON THE PANEL SCHEDULES NOT PART OF THE |
| | CALCULATIONS IG; WARMER, WATER HEATER, RANGE IN PANEL |
| | ?H?.ALSO THERE ARE LOADS FROM THE CABANA SERVICE |
| | LISTED IN THE HOUSE SERVICE CALCULATIONS. THESE |
| | SERVICES MUST BE CALCULATED AND LISTED SEPARATELY AS |
| | THEY ARE FROM SEPARATE SERVICES NOT SEPARATE PANELS ON |
| | THE SAME SERVICE. |
| | |
| | 7} REGARDING THE CABANA FLOOR PLAN SHEET E1, LOCATE THE |
| | WASHER AND DRYER LISTED ON THE PANEL SCHEDULE. |
| | |
| | 8} THE BATHROOM IN THE CABANA IS REQUIRED TO HAVE A |
| | CIRCUIT FOR THE RECEPTACLE SEPARATE PER 210 52(D). IT |
| | IS ON WITH OTHER RECEPTACLES OUTSIDE OF THAT ROOM. |
| | |
| | 9} THE LOFT BATHROOM MUST COMPLY WITH 210.52(D) |
| | RECEPTACLE REQUIREMENT. |
| | |
| | 10} THE LAUNDRY OFF THE MASTER BEDROOM MUST COMPLY WITH |
| | 210.11(C)(2), LAUNDRY BRANCH CIRCUIT. PANEL MUST BE |
| | LABELED INDICATING SAME PER 408.4. |
| | |
| | 11} ALL BEDROOM OUTLETS MUST COMPLY WITH 210.12 ARC |
| | FAULT PROTECTED. INDICATE IN THE PANELS. |
| | |
| | 12} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| | LOCATIONS OF REQUIRED ALARMS ON THE PLANS AND NOTE THE |
| | REQUIREMENT FOR INTERCONNECTING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |