| 2007-11-19 15:30:14 | RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. |
| | REVIEW DONE UNDER EXISTING BUILDING CODE 2004, FLORIDA |
| | RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3-A) NEW ADDITION NEEDS TO COMPLY WITH SEC. R302.1 |
| | AND R302.2 OF 2004 FLORIDA RESIDENTIAL CODE REGARDING |
| | WALL FIRE RATING, ROOF PROJECTIONS AND NO OPENINGS |
| | ALLOWED ON EAST WALL. |
| | |
| | B) SAME COMMENT APPLIES TO GARAGE RENOVATION AND |
| | ALTERATION ON WEST WALL. |
| | |
| | 4- PROVIDE SPECIFICATIONS FOR GARAGE SWING DOOR LEADING |
| | TO THE WORKROOM AREA FOR COMPLIANCE WITH SEC. R309.1 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- PROVIDE DETAILS/SPECS FOR SPIRAL STAIRS SHOWING |
| | COMPLIANCE WITHSEC. R311.5.8.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 6- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | NOTE: ATTACHMENT METHOD MUST MEET THE DESIGNER'S |
| | CALCULATED UPLIFT MOMENT. SEE PRODUCT APPROVAL. |
| | |
| | 7- PROVIDE COMPLETE DETAILS/SPECS FOR ORNAMENTAL |
| | GUARDRAIL TO VERIFY COMPLIANCE WITH TABLE R301.5 AND |
| | SEC. R312.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) ROOF TILE. |
| | |
| | B) ROOF TILE ADHESIVE IFSPECIFIED BY THE DESIGNER |
| | OF RECORD ON ITEM 6 ABOVE. SEE TILE PRODUCT APPROVAL |
| | FOR SPECIFICADHESIVE TO BE USED. |
| | |
| | C) FLAT ROOF. AND, CLEARLY SPECIFY WHICH APPROVED |
| | ASSEMBLY IS GOING TO BE INSTALLED.IF MORE THAN ONE |
| | FASTENING OPTION IS LISTED IN THE SELECTED APPROVED |
| | ASSEMBLY, THEN SPECIFY SELECTED FASTENING OPTION. ALSO, |
| | PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT THE |
| | PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION #7 |
| | ON PRODUCT APPROVAL.IF CALCULATIONS NEED TO BE DONE |
| | AND SEALED BY ARCHITECT OR ENGINEER, THEN PROVIDE SUCH |
| | CALCULATIONS. |
| | |
| | D) ARCHED DOORSAS SHOWN ON EXTERIOR ELEVATIONS. |
| | |
| | 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 10- PROVIDE COMPLETE SPECIFICATIONS FOR RAISED WOOD |
| | FLOOR IN GARAGE AREA AND RAISED WOOD FLOOR IN NEW |
| | ADDITION AREA TO SHOW COMPLIANCE WITH SECTIONS R319 |
| | (PROTECTION AGAINST DECAY),AND SEC. R408.1 THRU |
| | R408.3 OF 2004 FLORIDA RESIDENTIAL CODE (UNDER-FLOOR |
| | SPACE VENTILATION AND ACCESS). |
| | |
| | 11- ENERGY CALCULATIONS: |
| | A) PROVIDE SEPARATE ENERGY CALCULATIONS FOR GARAGE |
| | AND FOR NEW ADDITION AS REQUIRED BY SEC. 13-101.2.5.1 |
| | FBC 2004. |
| | NOTE: MAKE SURE CORRESPONDING A/C AREA IS USED FOR EACH |
| | BUILDING. |
| | |
| | B) NEED TO USE REVISED FORM 600A-200R. |
| | |
| | C) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | |
| | D) MAKE SURE CORRECT OVERHANG HEIGHT AND LENGTH IS |
| | USED. SEE ARCHITECTURAL PLANS AND REVISE AS REQUIRED. |
| | |
| | E) MAKE SURE CORRECT R-VALUES AE SHOWN FOR EXTERIOR |
| | WALLS. SEE SEC. 13-602.1.ABC.1 OF FBC 2004. |
| | |
| | 12- PROVIDE SOIL TEST REPORT.TWO COPIES. SEC. R401.4 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | NOTE: PLEASE MAKE SURE SOIL TEST REPORT HAS ENGINEER'S |
| | ORIGINAL SEAL AND SIGNATURE AND ENGINEERING FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER IS PROVIDED AS |
| | REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE |
| | CODE TO AVOID DELAYS. |
| | |
| | 13- SHEET A3.2: WALL SECTIONS CALLS FOR NEW 3/4" STUCCO |
| | ON PLAYWOOD ON METAL STUD FRAMED WALLS, WHILE |
| | STRUCTURAL DRAWINGS CALL FOR WOOD FRAMING. REVISE AS |
| | REQUIRED. |
| | NOTE: THIS COMMENT APPLIES TO WALL SECTIONS ON SHEETS |
| | A3.3,A3.4AND A3.5ALSO. |
| | REVISE AS REQUIRED. |
| | |
| | 14- SHEET A3.4:PROVIDE COMPLETE DETAIL/SPECS FOR |
| | INSTALLATION OF 1" BRICK PAVERS SET ON FLOATING WOOD |
| | DECK IN BALCONY.SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004 IN REFERENCE TO WIND LOADS SEC. R301 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 15- SHEET A5.0: PROVIDECOMPLETE SPECIFICATION FOR ALL |
| | FASTENERS TO BE USED ON SECTION/DETAIL 18 FOR CANOPY |
| | INSTALLATION. |
| | |
| | 16- SHEET A6.0:REVISE INSULATION SPECIFICATIONS ON |
| | ALL WALL ASSEMBLIES SHOWN ON THE WALL SCHEDULE. |
| | COORDINATE WITH ENERGY CALCULATIONS AND REVISE AS |
| | REQUIRED. |
| | |
| | 17- SHEET S-4: |
| | A) REVISE LOCATION OF ZONE 3 SHOWN ON DETAILB. SEE |
| | FIGURE 6-11C OF ASCE 7-02AND REVISE AS REQUIRED. |
| | |
| | B) DETAIL C : INFORMATION FOR ZONE 1,2 & 3 DOESN'T |
| | MATCH INFORMATION SHOWN BY 2X4 BLOCKING. ALSO, SEE SEC. |
| | R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR MINIMUM |
| | TYPE OF NAIL AND NAIL SPACING TO BE USED, INCLUDING |
| | NAIL SPACING IN ZONE 3 AREAS. REVISE ALL INFORMATION ON |
| | THIS DETAIL AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |