| Plan Review Notes For Permit 07110162 |
| Permit Number |
07110162 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-08 08:07:45 | 2004 FBC | | | ROOF FOR COVERED WALKWAY | | | | | | DENIED BY BUILDING | | | | | | ALTHOUGH THE INFORMATION SUBMITTED FOR THE ROOF SYSTEM | | | IS CODE COMPLIANT FOR INSTALLATION OVER A WOOD DECK, | | | THE APPROVED PLANS FOR THE COVERED WALK WAY ( SECTIONS | | | 4 AND 5 ON A1.2.4 AND S13) DO NOT SPECIFY A WOOD DECK | | | WITH A MODIFIED BITUMEN ROOF SYSTEM. THE PLANS FOR THE | | | MASTER PERMIT ( # 05121217) WILL NEED TO BE REVISED. | | | THE PERMIT FOR THE ROOF COVERING CAN NOT BE ISSUED | | | UNTIL THE REVISION HAS BEEN APPROVED. | | | | | | -ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|