| 2007-11-16 16:08:35 | |
| | |
| | APPLICATION #07110158 |
| | 3212 ALTON ROAD |
| | ELECTRICAL PLAN REVIEW |
| | WEST PALM BEACH, FL |
| | 11/16/07 |
| | . |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} THERE ARE TWO SHEETS NUMBERED 10.1., RENUMBER ONE TO |
| | MATCH THE SEQUENCE 106.1.3 FBC. |
| | |
| | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE |
| | DESIGN PROFESSIONAL IF EXEMPTIONS UNDER CHAPTER |
| | 471.003, FLORIDA STATUTES, IF EXEMPTIONS APPLY. |
| | |
| | 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. ALSO 210.12 DICTATES |
| | THEY BE ON AN ARC FAULT CIRCUIT. THE SMOKE DETECTOR |
| | CIRCUITS LISTED ON THE PLAN ARE 1) NOT ARC FAULT AND 2) |
| | ON MULTIPLE CIRCUITS, WHICH WOULD PROHIBIT THE REQUIRED |
| | INTERCONNECTION. |
| | |
| | 4} THE DINING ROOM CIRCUITS ARE MISMARKED AS 5 IN THE |
| | PANEL AND 7 AT THE RECEPTACLES. |
| | |
| | 5} DUE TO THE METER LOCATION, AND THE PANEL LISTED AS |
| | MLO, A DISCONNECT IS REQUIRED PER 230.70, 225.32. |
| | INDICATE LOCATION ON PLAN AND ADD TO THE RISER DIAGRAM, |
| | PER 230.72(A)(1) |
| | . |
| | 6} THE AIC RATING IS LISTED AS 22000 ON THE RISER AND |
| | 10000 IN THE PANEL. CORRELATE SAME. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |