| Plan Review Notes For Permit 07110133 |
| Permit Number |
07110133 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-21 11:15:11 | ***DENIED*** | | | | | | 1) THE ADDRESS ON THE PERMIT APPLICATION REFLECTS 800 | | | CLEMATIS ST. AND THE PLANS INDICATE 111 S. SAPODILLA | | | AVE. PLEASE CORRELATE AND ADD CORRECT ADDRESS TO ALL | | | APPLICABLE DOCUMENTS, IE. DRAWINGS, HYDRAULIC | | | CALCULATIONS, SPECIFICATION SHEETS ETC. | | | | | | 2) CALCULATION SHEETS INDICATE REQUIRED AND AVAILABLE | | | PRESSURE. PLEASE ADD THE WORD SAFETY MARGIN TO CALC | | | SHEETS IF THAT IS BEING REFERENCED. | | | | | | 3) DETAILS HAVE BEEN PROVIDED FOR A FIRE PUMP. PLEASE | | | INCLUDE MANUFACTURER SPECIFICATION OR CUT SHEETS FOR | | | EQUIPMENT. | | | | | | 4) STANDPIPE CONNECTIONS OR FDV'S TO BE 2 1/2"- 1 1/2" | | | REDUCER WITH CHAINS. PLEASE ADD TO DRAWINGS. | | | | | | 5) NEW FIRE DEPARTMENT CONNECTIONS TO BE SECURED WITH | | | KNOX LOCKING CAPS. | | | | | | 6) IF SPRINKLER SYSTEM CONNECTS TO A NEW DOUBLE | | | DETECTOR CHECK ASSEMBLY, PLEASE PROVIDE INFORMATION AND | | | DETAIL ON SPECIFIC EQUIPMENT. A NEW 6" FIRE DEPARTMENT | | | SERVICE IS SHOWN ON SHEET FP-1. IN ADDITION TO | | | ELECTRONIC SUPERVISION, CONTROL VALVES TO BE SECURED | | | WITH CHAIN AND LOCK. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|