Plan Review Notes
Plan Review Notes For Permit 07110133
Permit Number 07110133
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-21 11:15:11***DENIED***
  
 1) THE ADDRESS ON THE PERMIT APPLICATION REFLECTS 800
 CLEMATIS ST. AND THE PLANS INDICATE 111 S. SAPODILLA
 AVE. PLEASE CORRELATE AND ADD CORRECT ADDRESS TO ALL
 APPLICABLE DOCUMENTS, IE. DRAWINGS, HYDRAULIC
 CALCULATIONS, SPECIFICATION SHEETS ETC.
  
 2) CALCULATION SHEETS INDICATE REQUIRED AND AVAILABLE
 PRESSURE. PLEASE ADD THE WORD SAFETY MARGIN TO CALC
 SHEETS IF THAT IS BEING REFERENCED.
  
 3) DETAILS HAVE BEEN PROVIDED FOR A FIRE PUMP. PLEASE
 INCLUDE MANUFACTURER SPECIFICATION OR CUT SHEETS FOR
 EQUIPMENT.
  
 4) STANDPIPE CONNECTIONS OR FDV'S TO BE 2 1/2"- 1 1/2"
 REDUCER WITH CHAINS. PLEASE ADD TO DRAWINGS.
  
 5) NEW FIRE DEPARTMENT CONNECTIONS TO BE SECURED WITH
 KNOX LOCKING CAPS.
  
 6) IF SPRINKLER SYSTEM CONNECTS TO A NEW DOUBLE
 DETECTOR CHECK ASSEMBLY, PLEASE PROVIDE INFORMATION AND
 DETAIL ON SPECIFIC EQUIPMENT. A NEW 6" FIRE DEPARTMENT
 SERVICE IS SHOWN ON SHEET FP-1. IN ADDITION TO
 ELECTRONIC SUPERVISION, CONTROL VALVES TO BE SECURED
 WITH CHAIN AND LOCK.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756