| Date |
Text |
| 2008-01-18 10:27:59 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07110124 |
| | ADD: 2400 PRESIDENTIAL WAY #303 |
| | CONT: DELCO CONSTRUCTION & HOMES |
| | TEL: (561)436-4106 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND 1/18/08 |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) OK |
| | |
| | |
| | |
| | NOTE: THIS INFORMATION SHALL BE INDICATED ON THE |
| | PLANS. |
| | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 REVISIONS. INDICATE ON THE |
| | DRAWINGS WHICH CODE THE PLANS ARE DESIGN TO. THE PERSON |
| | RESPONSIBLE FOR THE DRAWINGS NEEDS TO DATE THE |
| | DRAWINGS. PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN |
| | SHOWING ELECTRICAL, MECHANICAL, PLUMBING AND STRUCTURAL |
| | CHANGES TO EXISTING FLOOR LAYOUT. PROVIDE THE LAYOUT OF |
| | THE ENTIRE UNIT TO SHOW SMOKE ALARM COMPLIANCE. |
| | |
| | NOTED: HOWEVER, NO CHANGES IN PEN, PENCIL OR WHITE-OUT |
| | IS ALLOWED ON THE PLANS. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR |
| | PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | 2)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. THIS APPEARS TO |
| | BE A LEVEL 2 ALTERATION. |
| | |
| | NOTE: OK |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |