| Plan Review Notes For Permit 07110114 |
| Permit Number |
07110114 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-08 14:23:57 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | 1.PLANS ARE TO BE IN ENGLISH AND ARE TO CLEARLY SHOW | | | SCOPE OF WORK WITH ALL REQUIRED DETAILS.PLANS WERE IN | | | SPANISH AND NO DETAILS PROVIDED. | | | | | | 2.PROVIDE A STRUCTURAL DETAIL FOR NEW OPENING. | | | | | | 3.PROVIDE A STRUCTURAL DETAIL FOR THE INFILL | | | (RELOCATED WINDOW). | | | | | | 4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3, | | | PROVIDE CALCULATIONS. | | | | | | 5.PROVIDE PRODUCT APPROVALS FOR THE DOOR. | | | | | | 6.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FAC61G15-23.002 (WIND LOADS). | | | | | | 7.WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER. | | | SUBMIT TWO COLLATED SETS OF PERMIT DOCUMENTS. |
|