2007-11-15 09:02:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE APPLICATION STATES THAT THIS WILL BE INSTALLED
 IN AUGUST 2003 BY OTHERS.WHAT DOES THIS MEAN?A
 PERMIT IS REQUIRED PRIOR TO COMMENCING WORK.
  
 2.THE SITE PLAN IS TO BE PREPARED BY A DESIGN
 PROFESSIONAL AS IT IS REQUIRED TO SHOW CODE COMPLIANCE,
 FBC*106.THIS MAY BE PREPARED BY THE ARCHITECT OR BY
 THE SURVEYOR.TWO SIGNED, SEALED, DATED ORIGINALS
 (WITH ORIGINAL SIGNATURES) WILL BE REQUIRED.(12/17/7
 - SITE PLAN NOT REQUIRED TO BE DONE BY DESIGN
 PROFESSIONAL BUT IF IT IS PREPARED BY AN ARCHITECT,
 ENGINEER, OR SURVEYOR AND IS REQUIRED TO SHOW CODE
 COMPLIANCE, MUST BE A SIGNED, SEALED, DATED ORIGINAL.)
  
 3.CVR, DESIGN PARAMETERS, STATES THAT THIS WILL
 COMPLY WITH 110MPH.THIS IS IN CONFLICT WITH CODE
 REQUIREMENTS AND OTHER PLACES ON THE PLAN, SEE FBC1609.
 THE CITY OF WEST PALM BEACH IS ENTIRELY IN THE 140MPH
 REGION.
  
 4.EXPOSURE B IS DECLARED.THE PLANS STATE THAT
 COASTAL IS EXPOSURE C.SEE FBC1609.4(3), AS THE
 DEFINITION OF EXPOSURE C HAS CHANGED EFFECTIVE DECEMBER
 8, 2006.ENGINEER IS TO EVALUATE SITE CONDITIONS AND
 PROVIDE JUSTIFICATION FOR EXPOSURE B.THIS MAY BE DONE
 BY REVISING THE SITE PLAN TO SHOW TERRAIN CONDITIONS
 AROUND THE PROPOSED IMPROVEMENT.
  
 5.DESIGN PARAMETERS, SHEET CVR, REFERS TO "APPLICABLE
 INTERNAL PRESSURE" BUT DOES NOT PROVIDE AN ENCLOSURE
 CLASSIFICATION OR COEFFICIENT, FBC1603.1.4.
  
 6.THE CERTIFICATE OF AUTHORIZATION FOR THE
 ARCHITECTURE FIRM IS TO BE PRINTED ON EACH SHEET,
 FAC61G16-23.002, 003.
  
 7.THIS AMENITY IS REQUIRED TO BE ACCESSIBLE, SEE
 FBC11-4.1.SHOW THE ACCESSIBLE ROUTE TO AND INTO THE
 GAZEBO, FBC11-4.1.6, FBC11-4.1.2.THE ACCESSIBLE ROUTE
 TO THE GAZEBO CAN BE SHOWN BY SPECIFYING MINIMUM WIDTH
 AND MAXIMUM SLOPE OF THE SIDEWALK LEADING TO THE
 GAZEBO.THE ROUTE INTO THE GAZEBO DOES NOT APPEAR TO
 BE COMPLIANT AS THERE IS A STEP UP INTO THE GAZEBO. SEE
 FBC11-4.3.8.
  
 8.THE NOA FOR THE SHINGLE ROOF REFERRED TO ON THE
 PLAN IS EXPIRED.PROVIDE CURRENT PRODUCT APPROVAL,
 FAC9B72.
  
 9.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE EVALUATION REPORT (NOA), FAC9B72.
 WWW.FLORIDABUILDING.ORG.PLEASE PROVIDE BOTH
 DOCUMENTS, TWO SETS.
  
 10. THE SHEATHING NAILING PATTERN ON A1 REFERS TO ZONE
 3 FOR GABLES.PLEASE SEE FBC FIGURE 1609.6.2.2; HIP
 ROOFS ALSO HAVE A ZONE 3 AND THE 4" EDGE NAILING IS
 APPLICABLE, FBC TABLE 2304.9.1(31).
  
 11.A1, OTHER PLACES, REFERS TO FBC2001, PLEASE
 REVISE.
  
 12.REVISE GOVERNING CODE TO INCLUDE 2007 AMENDMENTS
 (EFFECTIVE JULY 1, 2007).
  
 13.DECLARE OCCUPANCY CLASSIFICATION FBC CHAPTER 3.
  
 14.FLOOR LOADS HAVE BEEN DECLARED BUT INTIL OCCUPANCY
 HAS BEEN DECLARED, COMPLIANCE WITH FBC TABLE 1607.1
 CANNOT BE DETERMINED.
  
 15.ROOFING SYSTEM APPROVAL NOTES, A1, REFERS TO SOUTH
 FLORIDA BUILDING CODE 2004.THIS IS NOT GOVERNING CODE
 (AND DOES NOT EXIST).
  
 16.ROOFING SYSTEM APPROVAL NOTES, A1, REFERS TO MIAMI
 DADE PRODUCER 115.DO YOU MEAN RAS115?CHECK ALL
 NOTES AND REFERENCES.
  
 17.A19 IS HANDWRITTEN ON EACH SHEET.IT IS NOT CLEAR
 WHAT THIS IS; ARE THERE SHEETS MISSING FROM THE PLAN?
  
 18.PROVIDE PRODUCT APPROVAL FOR THE HELICAL SOIL
 ANCHORS, FAC9B72.NOTE THAT PRODUCT APPROVALS ARE TO
 BE APPROVED BY DESIGNER OF RECORD (SHOP DRAWING REVIEW
 STAMP, LETTER, OR SPECIFIC PRODUCT INCORPORATED INTO
 THE PLAN), FBC*106.3.3.
  
 19.A2 SHOWS CEDAR SHAKE SHINGLE; OTHER SHOW 5TAB
 ASPHALT.PLEASE REVISE CONFLICT.
  
 20.FLOOR FRAMING SURFACE IS TO COMPLY WITH FBC11-4.5.
 SHOW MAXIMUM GAPS AT BOARD JOINTS.
  
 21.PRODUCT APPROVALS REQUIRED FOR THE LOUVERS,
 FAC9B72.
  
 22.NO (ACCESS) OPENING IN THE GAZEBO RAILING SHOWN.
 SHOW LOCATION AND WIDTH, FBC10.
  
 23.THE RAILING FOR THE GAZEBO IS TO COMPLY WITH
 FBC1012.1.PROVIDE DESIGN CRITERIA SHOWING COMPLIANCE
 WITH FBC1012 AND FBC1607.7.