| Plan Review Notes For Permit 07110082 |
| Permit Number |
07110082 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-08-22 15:09:52 | REVISION SHEET MEP-1 SANITRY RISER DIAGRAM: "OK" ADDED | | | AIR ADMITTANCE VALVES (STUDOR VENTS) TO PLUMBING. | | | | | | ****************PROVISO**************** | | | (A) PER FBC-2004 PLUMBING SECTION 406.3 WASTE | | | CONNECTIONS. THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN | | | SHALL CONNECT TO A BRANCH DRAIN OR DRAINAGE STACK A | | | MINIMUM OF 3 INCHES (76MM) IN DIAMETER. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|