| 2007-11-09 16:29:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) MECHANICAL PLAN PAGE M1 SCALE SHOWS 1/4"-1'0". PLAN | | | IS NOT SCALED TO 1/4" PLEASE CORRECT. PLEASE TRY TO | | | ENLARGE MECH. PLAN M1 TO SHOW ADDITION DUCT LAYOUT | | | EASIER TO READ. | | | | | | 3) COOLING LOAD CALCULATIONS ARE CALLING FOR 15,558 | | | TOTAL BTU'S, MECHANICAL PLAN PAGE M1 SHOWS TOTAL BTU'S | | | AT 23,000. THE PLANS CAN ONLY CALL FOR 15% MORE TOTAL | | | BTU'S THAN THE COOLING LOAD CAL'S. SEE 2004 FBC | | | 13-607.1.ABC.1.1 PLEASE CORRECT. A 1.5 TON SYSTEM MAY | | | MEET YOUR REQUIREMENTS. | | | | | | 4) SHOW WERE THE CLOTHES DRYER VENT WILL TERMINATE ON | | | MECHANICAL PLANS, SEE 2004 FBC/R R303.4.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|