Plan Review Notes For Permit 07110058
Permit Number 07110058
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-12-20 14:14:13*****DENIED*****
  
 THE FOLLOWING COMMENTS (OF TEN) TAKEN FROM THE PREVIOUS
 FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED.CAPS
 SUGGESTS HOW ITEM MAY BE ADDRESSED
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 NFPA 241 TO CODE ANALYSIS, SHEET A3
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).ADD
 TO GENERAL NOTES, SHEET A1
  
 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM
 THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.ADD TO GENERAL NOTES,
 SHEET A1
  
 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF
 THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH.ADD COMMENT TO AN
 APPROPIATE PLAN SHEET
  
 07.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
 PLEASE SPECIFY
  
 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL
 DISTANCE.COULD NOT LOCATE FIRE EXTINGUISHERS ON SHEET
 A2AS PER YOUR RESPONSE LETTER
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW