| 2007-12-20 14:14:13 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS (OF TEN) TAKEN FROM THE PREVIOUS |
| | FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED.CAPS |
| | SUGGESTS HOW ITEM MAY BE ADDRESSED |
| | |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| | NFPA 241 TO CODE ANALYSIS, SHEET A3 |
| | |
| | 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY |
| | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).ADD |
| | TO GENERAL NOTES, SHEET A1 |
| | |
| | 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM |
| | THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS |
| | NECESSARY FOR SAFE OPERATION.ADD TO GENERAL NOTES, |
| | SHEET A1 |
| | |
| | 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF |
| | THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT |
| | AND NO LESS THAN 1" IN WIDTH.ADD COMMENT TO AN |
| | APPROPIATE PLAN SHEET |
| | |
| | 07.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS |
| | IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY |
| | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II. |
| | PLEASE SPECIFY |
| | |
| | 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL |
| | DISTANCE.COULD NOT LOCATE FIRE EXTINGUISHERS ON SHEET |
| | A2AS PER YOUR RESPONSE LETTER |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |