2007-12-20 18:21:532004 FBC W/2007 REVISIONS
 CHANGE OF OCCUPANCY FROM R3 TO MIXED OCCUPANCY
 R3/BUSINESS
  
 DENIED BY BUILDING
  
 1)THE VALUE OF THE WORK ON THE APPLICATION MAY BE TOO
 LOW. ADDITIONAL WORK MAY BE REQUIRED TO ACHIEVE CODE
 COMPLIANCE FOR THE CHANGE OF OCCUPANCY. THE PLANS DO
 NOT CLEARLY INDICATE THE SCOPE OF WORK THAT WILL BE
 DONE. PROVIDE AN ITEMIZED LIST OF WHAT IS TO BE DONE
 UNDER THIS PERMIT ON THE PLANS. SEE FBC 106.1.1THE
 VALUE OF THE WORK WILL BE DETERMINED BY THE SCOPE OF
 THE PROPOSED WORK.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) COMPLIED
  
 4) THE PLANS DO NOT ADEQUATELY INDICATE THE EXISTING
 CONDITIONS, ACCORDING TO THE PRE-INSPECTION REPORT THAT
 WAS SUBMITTED BY DOUG ROBERTSON. 1) THE ENTRY DOOR IS A
 SINGLE DOOR. (2) BREAK ROOM DOESN'T HAVE SINK OR RANGE.
 (3) STAIRS ARE 32" WIDE. (4)ON THE SECOND FLOOR THERE
 IS NO WALL BETWEEN THE STUDY AND THE BEDROOM. PLEASE
 SUBMIT PLANS THAT ACCURATELY INDICATE THE THE
 CONDITIONS. FBC 106.1.1* CITY AMENDMENTS. PROVIDE
 DRAWINGS THAT SHOWS EXACTLY WHAT IS EXISTING AND
 DRAWINGS SHOWING WHAT NEW WORK WILL BE DONE.
  
 5) THE BUILDING PLAN REVIEW WAS DONE BASED ON THE PLANS
 THAT WERE SUBMITTED.
  
 6) SPECIFY THE LIVE LOAD CAPACITY OF THE FIRST FLOOR.
 OFFICES REQUIRE A MINIMUM UNIFORMLY DISTRIBUTED LIVE
 LOAD OF 50 PSF. SEE FBC TABLE 1607.1.
  
 7) COMPLIED
  
 8) COMPLIED
  
 9) SHOW COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS FOR
 DOORS FBC 11-4.1.3(7), 11-4.3.9 AND 11-4.13. SPECIFY
 THE SIZES OF THE DOORS ON THE PLANS AND THAT THE DOOR
 HARDWARE AND THRESHOLDS COMPLY WITH ACCESSIBILTY
 REQUIREMENTS.
  
 10) FBC EXISTING BUILDING 812.5 REQUIRES THE NEW
 OCCUPANCY TO COMPLY WITH FBC CHAPTER 11 FOR
 ACCESSIBILITY. ALSO SEE 11-4.1.6 SHOW COMPLIANCE WITH
 FBC 1007 FOR ACCESSIBLE MEANS OF EGRESS. (SEE COMMENT
 #11).
  
 11) SHOW COMPLIANCE WITH 11-4.1.3(8)AND (9) FOR
 ACCESSIBLE ENTRANCES. THESE SECTIONS REQUIRE THE NUMBER
 OF ACCESSIBLE ENTRANCES IN A NUMBER EQUIVALENT TO THE
 NUMBER OF REQUIRED EXITS. FBC 1013.2 PROHIBITS EGRESS
 THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED
 FOR SIMILAR PURPOSES. THEREFORE, YOU WILL NEED TO
 ELIMINATE THE STOVE FROM THE BREAK ROOM OR PROVIDE
 ANOTHER ACCESSIBLE ENTRANCE.
  
 12) SHOW COMPLIANCE WITH FBC 11-4.3 FOR ACCESSIBLE
 ROUTE. PROVIDE SITE PLAN WITH DIMENSIONS OF WALKS, CURB
 RAMPS, RAMPS, LANDINGS, ETC. SPECIFIED. PROVIDE
 ELEVATIONS WITH DIMENSIONS INDICATING THE HEIGHTS ABOVE
 GRADE. SPECIFY THE WIDTH OF THE WALKWAY TO THE
 ACCESSIBLE ENTRANCE, SPECIFY THE SLOPE OF THE WALK,
 ETC. IF THERE IS A RAMP PROVIDE A DETAIL OF IT.
 INDICATE THE FINISH FLOOR HEIGHT OF THE STRUCTURE ABOVE
 GRADE AT THE ENTRANCES.
  
 13) COMPLIED
  
 14) COMPLIED
  
 NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES
 OF THESE COMMENTS.
  