Plan Review Notes
Plan Review Notes For Permit 07110058
Permit Number 07110058
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-15 12:38:34*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM
 THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 04.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF
 THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH.
  
 06.PROVIDE THE OCCUPANT LOAD (NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED)
 BASED UPON THE CHARACTERISTICS OF THE USE OF THE SPACE
 OR AS DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF
 THE SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
 07.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
  
 08.IT IS ILLUSTRATED ON THE SECOND FLOOR (SEE SHEET
 A3) OF SEVERAL SMOKE DETECTORS (SD);CLARIFY AS TO
 WHETHER THESE DEVICES ARE INDEED SMOKE DETECTORS OR
 SMOKE ALARMS.PLEASE BE ADVISED THAT SMOKE DETECTORS
 (SD) ARE TIED INTO THE BUILDING'S FIRE ALARM SYSTEM,
 WHEREAS SMOKE ALARMS (SA) SOUND ONLY WITHIN AN
 INDIVIDUAL DWELLING UNIT OR SUITE OF ROOMS AND SHALL
 NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
  
 09.WHEN SMOKE ALARMS ARE INSTALLED IN NEW
 CONSTRUCTION, THEY SHALL BE ARRANGED SO THAT THE
 OPERATION OF ANY SMOKE ALARM SHALL CAUSE THE ALARM
 WITHIN THE DWELLING UNIT, SUITE OF ROOMS, OR SIMILAR
 AREA TO SOUND.
  
 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722