| 2007-11-13 17:41:34 | |
| | |
| | APPLICATION # 07110058 |
| | ELECTRICAL PLAN REVIEW |
| | 311 11TH STREET |
| | 11/13/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | |
| | 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | DEVICES AND LIGHTING. |
| | |
| | 3} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER |
| | ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE |
| | WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 4} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND |
| | CONDUCTOR SIZES. PLEASE SEE NEW VERBIAGE FOR 2005 NEC: |
| | "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO |
| | ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL |
| | OTHERS." PHRASES LIKE ?GENERAL LIGHTING? ARE TOO VAGUE |
| | TO LOCATE THE DISCONNECTING MEANS FOR A CIRCUIT OR |
| | PIECE OF EQUIPMENT AS IS THE INTENT OF THIS ARTICLE. |
| | |
| | 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| | (2003), AND CIRCUITED |
| | PER 700.12 NEC (F)(4). INDICATE SAME ON PLANS. SEE |
| | COMMENT #2. |
| | |
| | 6} THE KITCHEN RECEPTACLES MUST COMPLY WITH |
| | 210.8(B)(2), GFI PROTECTED. INDICATE ON THE PLANS. |
| | |
| | 7} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | |
| | 8} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS |
| | AMENDED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |