2007-12-11 11:46:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NOT NOTICED IN LAST REVIEW: THE EXISTING OUTSIDE AIR
 DUCT PENETRATING THE WEST RATED WALL OF THE CONFERENCE
 ROOM NEEDS TO COMPLY WITH 2004 FBC/M 607.5.3OR FBC
 712.3. PLEASE PROVIDE A FIRE DAMPER OR SHOW A DETAIL OF
 THE FIRE STOP SYSTEM TO BE USED.
  