| Plan Review Notes For Permit 07110044 |
| Permit Number |
07110044 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-11 11:46:43 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) NOT NOTICED IN LAST REVIEW: THE EXISTING OUTSIDE AIR | | | DUCT PENETRATING THE WEST RATED WALL OF THE CONFERENCE | | | ROOM NEEDS TO COMPLY WITH 2004 FBC/M 607.5.3OR FBC | | | 712.3. PLEASE PROVIDE A FIRE DAMPER OR SHOW A DETAIL OF | | | THE FIRE STOP SYSTEM TO BE USED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|