Text |
| 2007-11-17 10:34:02 | DENIED; | | | 1. INDICATE MATERIAL TO BE USED, FOR SANITARY AND WATER | | | PIPING. | | | 2. PAGE P-1 GENERALSPECIFICATIONS NOTE 22. AIR CHAMBER | | | ARE NOTAPPROVED PLUMBING PRODUCT. CHANGE NOTE TO | | | READ WATER HAMMER ARRESTORS. | | | 3. BREAK SINK MUST MEET ALL HANDICAP REQUIREMENTS SEE | | | FBC BUILDING CHAPTER 10SECTIONS 11-4.24.1 THRU | | | 11-4.24.7. SHOW ON DETAIL. | | | A) 11-4.24.3 KNEE CLEARANCE UNDER SINK | | | MUST BE 30 X 27 X 19. CABINET DOORS CANNOT BE IN THE | | | CLEAR FLOOR SPACE. | | | B)11-4.24.4 SHOW THE DEPTH OF THE SINK. | | | (MAX OF 6 1/2" DEEP. | | | C) 11-4.24.5 SHOW CLEAR FLOOR SPACE ON | | | FLOOR PLAN. | | | D)11-4.24.6 ADD NOTE TO RAP TRAP. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|