Plan Review Notes
Plan Review Notes For Permit 07110044
Permit Number 07110044
Review Stop P
Sequence Number 1
Notes
Date Text
2007-11-17 10:34:02DENIED;
 1. INDICATE MATERIAL TO BE USED, FOR SANITARY AND WATER
 PIPING.
 2. PAGE P-1 GENERALSPECIFICATIONS NOTE 22. AIR CHAMBER
 ARE NOTAPPROVED PLUMBING PRODUCT. CHANGE NOTE TO
 READ WATER HAMMER ARRESTORS.
 3. BREAK SINK MUST MEET ALL HANDICAP REQUIREMENTS SEE
 FBC BUILDING CHAPTER 10SECTIONS 11-4.24.1 THRU
 11-4.24.7. SHOW ON DETAIL.
 A) 11-4.24.3 KNEE CLEARANCE UNDER SINK
 MUST BE 30 X 27 X 19. CABINET DOORS CANNOT BE IN THE
 CLEAR FLOOR SPACE.
 B)11-4.24.4 SHOW THE DEPTH OF THE SINK.
 (MAX OF 6 1/2" DEEP.
 C) 11-4.24.5 SHOW CLEAR FLOOR SPACE ON
 FLOOR PLAN.
 D)11-4.24.6 ADD NOTE TO RAP TRAP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695