| 2007-11-14 08:43:17 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) INFORMATION MISSING FROM TITLE BLOCK. |
| | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND |
| | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. |
| | |
| | 2) PROVIDE RETURN AIR TO BOTH CONFERENCE ROOMS, SEE |
| | 2004 FBC/M 601.4. |
| | |
| | 3) PROVIDE RETURN AIR TO OFFICE (YELLOW HIGH LIGHTED ON |
| | MECHANICAL PLAN), SEE 2004 FBC/M 601.4. |
| | |
| | 4) SEE YELLOW HIGH LIGHT ON PAGE M2 SHOWING RETURN AIR |
| | GRILL IN HALL WITH NO DUCT TO IT, PLEASE EXPLAIN OR |
| | CORRECT. |
| | |
| | 5) ENERGY CALCULATIONS COVER SHEET SHOWS MAX TONNAGE AS |
| | 0. THREE A/C SYSTEMS ARE BEING INSTALLED, SEE 2004 FBC |
| | 13-103.2, PLEASE CORRECT. |
| | |
| | 6) ENERGY CALCULATIONS PAGE 4 SHOWS SPACE COOLING |
| | DESIGN IS $2. AND REFERENCE IS $0. AGAIN THREE SYSTEMS |
| | ARE BEING INSTALLED, ALSO CHECK AND CORRECT VENT FANS. |
| | SEE 2004 FBC 13-103.2. |
| | |
| | 7) ENERGY CALCULATIONS PAGE 5 SHOWS ONLY ONE A/C |
| | SYSTEM, THREE ARE BEING INSTALLED, PLEASE CORRECT. SEE |
| | 2004 FBC 13-103.2. |
| | |
| | MECHANICAL PLAN REVIEW BY; |