Plan Review Notes
Plan Review Notes For Permit 07110044
Permit Number 07110044
Review Stop M
Sequence Number 1
Notes
Date Text
2007-11-14 08:43:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) PROVIDE RETURN AIR TO BOTH CONFERENCE ROOMS, SEE
 2004 FBC/M 601.4.
  
 3) PROVIDE RETURN AIR TO OFFICE (YELLOW HIGH LIGHTED ON
 MECHANICAL PLAN), SEE 2004 FBC/M 601.4.
  
 4) SEE YELLOW HIGH LIGHT ON PAGE M2 SHOWING RETURN AIR
 GRILL IN HALL WITH NO DUCT TO IT, PLEASE EXPLAIN OR
 CORRECT.
  
 5) ENERGY CALCULATIONS COVER SHEET SHOWS MAX TONNAGE AS
 0. THREE A/C SYSTEMS ARE BEING INSTALLED, SEE 2004 FBC
 13-103.2, PLEASE CORRECT.
  
 6) ENERGY CALCULATIONS PAGE 4 SHOWS SPACE COOLING
 DESIGN IS $2. AND REFERENCE IS $0. AGAIN THREE SYSTEMS
 ARE BEING INSTALLED, ALSO CHECK AND CORRECT VENT FANS.
 SEE 2004 FBC 13-103.2.
  
 7) ENERGY CALCULATIONS PAGE 5 SHOWS ONLY ONE A/C
 SYSTEM, THREE ARE BEING INSTALLED, PLEASE CORRECT. SEE
 2004 FBC 13-103.2.
  