| Plan Review Notes For Permit 07110044 |
| Permit Number |
07110044 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-14 11:20:31 | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 3. EXITS ARE TO BE MAINTAINED DURING CONSTRUCTION. | | | | | | 4. EXISTING FIRE SAFETY SYSTEMS AND DEVICES SHALL NOT | | | BE RENDERED OUT OF SERVICE. ANY TEMPORARY NEED TO PLACE | | | THESE SYSTEMS OUT OF SERVICE FOR GREATER THAN FOUR | | | HOURS IN A TWENTY FOUR HOUR PERIOD REQUIRES A FIRE | | | WATCH. ALL FIRE WATCHES MUST BE SUBMITTED IN WRITING TO | | | THE BATTALION CHIEF OF FIRE PREVENTION OR THE ASSISTANT | | | FIRE MARSHAL PRIOR TO NEEDING FIRE WATCH ACTIVITIES. | | | | | | 5. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | | SPRINKLER SYSTEM REMODEL. | | | | | | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY | | | MODIFICATIONS TO THE EXISTING FIRE ALARM SYSTEM. | | | | | | 7. NO REFRIGERANT LINES ARE TO ENTER OR TRAVEL THROUGH | | | ANY EXIT STAIRS ON THE BUILDING. | | | | | | 8. AS ALWAYS ALL WORK IS SUBJECT TO FIELD INSPECTION | | | AND APPROVAL BY CITY INSPECTORS. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|