 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE CIRCUIT NUMBERS FOR THE CONDENSING UNITS ON
 SHEET E3 DO NOT CORRELATE WITH THE PANEL SCHEDULE.
  
 2} SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 1
 FLUORESCENT, PLEASE INDICATE COMPLIANCE WITH ALL
 FIXTURES TO BE USED.
  
 3} INDICATE WHAT TABLE THE 1.0 LPD FOR THE HALLWAY WAS
 DERIVED. SHEETE1, "LIGHT LEVEL VERIFICATION" CHART.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  