| 2007-11-28 19:19:35 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. M-2: KEY NOTE #10, ARE REFRIGERANT LINES PENETRATING | | | RATED FLOOR/CEILING ASSEMBLIES TO GET TO ROOF? IF SO, | | | PROVIDE DETAIL FOR THROUGH-PENETRATION FIRESTOP SYSTEM | | | IN COMPLIANCE WITH FBC 712.4.1.2. | | | | | | 2. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL | | | BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR | | | EXHAUST IN ACCORDANCE WITH FBC, M CHAPTER 4 PER THE | | | REQUIREMENTS OF FBC, EB 609.1. PROVIDE OUTSIDE AIR | | | CALCULATIONS SHOWING VENTILATION REQUIREMENTS INCLUDING | | | OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, CFM REQUIRED | | | AND CFM PROVIDED IN ACCORDANCE WITH FBC, M TABLE | | | 403.3. | | | | | | 3. M-3: PRE-ENGINEERED A/C STANDS ARE DEFINED AS | | | STRUCTURAL COMPONENTS UNDER FAC RULE 9B-72 AND AS SUCH | | | A PRODUCT APPROVAL IS REQUIRED. PROVIDE A PRODUCT | | | APPROVAL FOR THE SPECIFIC STAND TO BE INSTALLED ALONG | | | WITH INSTALLATION INSTRUCTIONS. THE STAND IS TO BE | | | SECURED TO THE STRUCTURE AND THE CONDENSING UNIT IS TO | | | BE ATTACHED TO THE STAND PER THE INSTRUCTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|