Plan Review Notes
Plan Review Notes For Permit 07110013
Permit Number 07110013
Review Stop M
Sequence Number 2
Notes
Date Text
2008-02-13 10:20:581. PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. HOWEVER, REVIEW STOP WILL BE IN "FAIL" STATUS
 PENDING BUILDING PLAN REVIEW OF PRODUCT APPROVAL FOR
 THE PRE-ENGINEERED A/C STAND. THE PAPERWORK SUBMITTED
 DOES NOT APPEAR TO BE AN ACTUAL PRODUCT APPROVAL BUT
 SOME PAPERWORK FROM THE MANUFACTURER. ALSO, THE
 SUBMITTAL IS OF POOR QUALITY AND IS ILLEGIBLE.
  
 2. ENERGY CALCULATIONS HAVE NOT BEEN REVIEWED FOR
 COMPLIANCE WITH MECHANICAL REQUIREMENTS OF FBC CHAPTER
 13. METHOD B CALCULATIONS ARE NOT AN OPTION AS THIS IS
 NOT A RENOVATION AS DEFINED IN FBC 13-202. SEE FBC
 13-400.0.C.4 THEREFORE, ONLY MINIMUM EFFICIENCY
 CRITERIA FOR NEWLY INSTALLED EQUIPMENT NEED BE
 DEMONSTRATED. THIS INFORMATION IS ON THE PLANS AND IS
 DEEMED COMPLIANT.