| 2008-02-13 10:20:58 | 1. PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND | | | STAMPED. HOWEVER, REVIEW STOP WILL BE IN "FAIL" STATUS | | | PENDING BUILDING PLAN REVIEW OF PRODUCT APPROVAL FOR | | | THE PRE-ENGINEERED A/C STAND. THE PAPERWORK SUBMITTED | | | DOES NOT APPEAR TO BE AN ACTUAL PRODUCT APPROVAL BUT | | | SOME PAPERWORK FROM THE MANUFACTURER. ALSO, THE | | | SUBMITTAL IS OF POOR QUALITY AND IS ILLEGIBLE. | | | | | | 2. ENERGY CALCULATIONS HAVE NOT BEEN REVIEWED FOR | | | COMPLIANCE WITH MECHANICAL REQUIREMENTS OF FBC CHAPTER | | | 13. METHOD B CALCULATIONS ARE NOT AN OPTION AS THIS IS | | | NOT A RENOVATION AS DEFINED IN FBC 13-202. SEE FBC | | | 13-400.0.C.4 THEREFORE, ONLY MINIMUM EFFICIENCY | | | CRITERIA FOR NEWLY INSTALLED EQUIPMENT NEED BE | | | DEMONSTRATED. THIS INFORMATION IS ON THE PLANS AND IS | | | DEEMED COMPLIANT. |
|