Plan Review Notes
Plan Review Notes For Permit 07110013
Permit Number 07110013
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-23 10:23:04 
  
 ** DENIED2ND REVIEW **
  
 1) NOTE: PLEASE SEE THE METHOD *B* FLA COM CALCULATIONS
 AND INPUT DATA REPORT DOES NOT MATCH WITH PLANS. FOR
 EXAMPLE: PLEASE SEE THE IDR ONLY INDICATES ONE FIXTURE
 WHICH IS NOT POSSIBLE WHEN THE PLANS CONTAIN NUMEROUS
 FIXTURES.
 EACH FIXTURE, WATTAGE AND METHOD OF CONTROL NEEDS TO
 COORDINATE WITH PLANS.
 13-415.2, 13-415.1.B
  
 ** ELECTRICAL PLANS ARE OK AND HAVE BEEN STAMPED. NEED
 TO ADDRESS #1 ABOVE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]