| 2007-12-01 15:37:22 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. LEVEL OF ALTERATION SHALL BE DECLARED BY THE |
| | DESIGNER IN ACCORDANCE WITH FBC, EB 301.5. THIS APPEARS |
| | TO BE A LEVEL 2 ALTERATION AND SHALL BE REVIEWED AS |
| | SUCH. |
| | |
| | 2. ENERGY CALCULATIONS: METHOD A COMPLIANCE IS NOT |
| | APPLICABLE FOR THIS PROJECT. EXISTING BUILDINGS NOT |
| | MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW |
| | HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING |
| | SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE |
| | MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE |
| | SYSTEM(S) BEING CHANGED IN ACCORDANCE WITH FBC |
| | 13-400.0.C.4. DEMONSTRATE COMPLIANCE BY SHOWING ALL |
| | NEWLY INSTALLED BUILDING ENVELOPE COMPONENTS, |
| | MECHANICAL AND ELECTRICAL SYSTEMS MEET THE PRESCRIPTIVE |
| | MINIMUM EFFICIENCIES REQUIRED BY FBC SECTION 13-4. |
| | NOTE: SYSTEM SIZING SUMMARY ATTACHED TO METHOD A FORM |
| | IS OK AND MAY BE USED TO SHOW COMPLIANCE WITH FBC |
| | 13-407.1.ABC.1. |
| | |
| | 3. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL |
| | BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR |
| | EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL. SHOW COMPLIANCE WITH FBC, M TABLE 403.3 OR |
| | ASHRAE 62.1-2004 UNLESS MEANS FOR NATURAL VENTILATION |
| | ARE PRESENT AS ALLOWED UNDER FBC, M SEC.402. THIS |
| | APPLIES TO ALL HABITABLE AREAS OF THIS FLOOR. |
| | |
| | 4. OUTSIDE AIR CALCULATIONS: NOTE CALLS FOR ASHRAE |
| | STANDARD 62 AND FMC 403.3. ONE METHOD OF VENTILATION OR |
| | THE OTHER SHALL BE DECLARED AND A COMBINATION OF THE |
| | TWO SHALL NOT BE USED IN ACCORDANCE WITH FBC, M 403.4. |
| | |
| | 5. COND. UNIT SUPPORT DETAIL: IS THIS TO BE A SITE |
| | BUILT STAND OR A PRE-ENGINEERED SYSTEM? IF A |
| | PRE-ENGINEERED STAND IS TO BE USED, PRODUCT APPROVAL IS |
| | REQUIRED AS THESE STANDS HAVE BEEN DEFINED AS |
| | STRUCTURAL COMPONENTS UNDER FAC RULE 9B-72. PROVIDE A |
| | PRODUCT APPROVAL FOR THE SPECIFIC STAND TO BE USED. FOR |
| | MORE INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM |
| | PLEASE VISIT: WWW.FLORIDABUILDING.ORG |
| | |
| | 6. IF NEW CONDENSING UNIT IS INSTALLED WITHIN 10 FEET |
| | OF AN OPEN ROOF EDGE, PROVIDE GUARDS FOR SERVICE ACCESS |
| | IN ACCORDANCE WITH FBC, M 304.10. |
| | |