Plan Review Notes
Plan Review Notes For Permit 07110013
Permit Number 07110013
Review Stop M
Sequence Number 1
Notes
Date Text
2007-12-01 15:37:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. LEVEL OF ALTERATION SHALL BE DECLARED BY THE
 DESIGNER IN ACCORDANCE WITH FBC, EB 301.5. THIS APPEARS
 TO BE A LEVEL 2 ALTERATION AND SHALL BE REVIEWED AS
 SUCH.
  
 2. ENERGY CALCULATIONS: METHOD A COMPLIANCE IS NOT
 APPLICABLE FOR THIS PROJECT. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED IN ACCORDANCE WITH FBC
 13-400.0.C.4. DEMONSTRATE COMPLIANCE BY SHOWING ALL
 NEWLY INSTALLED BUILDING ENVELOPE COMPONENTS,
 MECHANICAL AND ELECTRICAL SYSTEMS MEET THE PRESCRIPTIVE
 MINIMUM EFFICIENCIES REQUIRED BY FBC SECTION 13-4.
 NOTE: SYSTEM SIZING SUMMARY ATTACHED TO METHOD A FORM
 IS OK AND MAY BE USED TO SHOW COMPLIANCE WITH FBC
 13-407.1.ABC.1.
  
 3. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL
 BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SHOW COMPLIANCE WITH FBC, M TABLE 403.3 OR
 ASHRAE 62.1-2004 UNLESS MEANS FOR NATURAL VENTILATION
 ARE PRESENT AS ALLOWED UNDER FBC, M SEC.402. THIS
 APPLIES TO ALL HABITABLE AREAS OF THIS FLOOR.
  
 4. OUTSIDE AIR CALCULATIONS: NOTE CALLS FOR ASHRAE
 STANDARD 62 AND FMC 403.3. ONE METHOD OF VENTILATION OR
 THE OTHER SHALL BE DECLARED AND A COMBINATION OF THE
 TWO SHALL NOT BE USED IN ACCORDANCE WITH FBC, M 403.4.
  
 5. COND. UNIT SUPPORT DETAIL: IS THIS TO BE A SITE
 BUILT STAND OR A PRE-ENGINEERED SYSTEM? IF A
 PRE-ENGINEERED STAND IS TO BE USED, PRODUCT APPROVAL IS
 REQUIRED AS THESE STANDS HAVE BEEN DEFINED AS
 STRUCTURAL COMPONENTS UNDER FAC RULE 9B-72. PROVIDE A
 PRODUCT APPROVAL FOR THE SPECIFIC STAND TO BE USED. FOR
 MORE INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM
 PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 6. IF NEW CONDENSING UNIT IS INSTALLED WITHIN 10 FEET
 OF AN OPEN ROOF EDGE, PROVIDE GUARDS FOR SERVICE ACCESS
 IN ACCORDANCE WITH FBC, M 304.10.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]