| Date |
Text |
| 2007-11-19 16:36:51 | *****DENIED***** | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.PROJECT LOCATION UNCLEAR;THE ATTACHED | | | ENERGY/GAUGE SHEETS INDICATE THE 3RD FLOOR, WHEREAS THE | | | PLAN SHEETS INDICATE RENOVATION FOR THE 2ND AND 3RD | | | FLOORS. | | | | | | 3.BASED UPON A FIELD SURVEY CONDUCTED BY THIS WRITER, | | | IT WOULD APPEAR THAT THE TYPE OF OCCUPANCY FOR THE | | | PROJECT IS ASSEMBLY.PLEASE CLARIFY. | | | | | | 4.PLEASE INCLUDE A LIFE SAFETY PLAN SHEET(S) WHICH | | | SHALL SHOW THE TRAVEL DISTANCE TO REACH THE EXITS. | | | | | | 5.ON SHEET A-2.1 AND A-2.2, PLEASE EXPLAIN RATIONALE | | | FOR THE CLOSING OF THE EXISTING STAIR AT THE LOWER | | | LEVEL. | | | | | | 6.SEPARATE PLANS AND PERMIT SHALL BE REQUIRED FOR THE | | | FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|