| Date |
Text |
| 2007-11-28 14:52:07 | ** DENIED** |
| | |
| | |
| | 1) NOTE: PLEASE SEE CODES SHALL BE STATED ON PLANS FOR |
| | RELEVANT DESIGNS. |
| | PLEASE INCLUDE THE FOLLOWING. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** ALSO REQUIRED ON ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE COORDINATE ALL SCOPE OF WORK ON |
| | APPLICATION AND PLANS WITH THAT OF PERMITTED WORK |
| | ALREADY ISSUED FOR BUILDING. |
| | PLEASE KNOW FOR EXAMPLE, STAIRS ON 2ND FLOOR ARE NO |
| | LONGER GOING TO DEAD ON FIRST FLOOR, WALL IS BEING |
| | REMOVED, ELECTRICAL LIGHTING AS SHOWN IS CHANGING ETC |
| | ETC. |
| | PLEASE KNOW THIS WORK IS FOR TENANT COMMON AREAS. |
| | PLEASE ALSO KNOW THIS LOCATION IS PART OF A LARGER |
| | BUILDING AND IS NO LONGER ONE BUILDING BY DEFINITION AS |
| | OLD PREVIOUS FIRE WALLS ARE NO LONGER IN EXISTENCE. |
| | |
| | 3) NOTE: PLEASE SEE THE METHOD *A* WHOLE BUILDING |
| | CALCULATIONS CAN NOT BE USED AS THE WHOLE BUILDING IS |
| | NOT BEING BROUGHT INTO COMPLIANCE. |
| | PLEASE KNOW FOR ELECTRICAL LIGHTING PERFORMANCE |
| | CALCULATIONS ARE NEEDED PER 13-415.2 |
| | PLEASE ALSO PLACE NOTES ON PLANS AS REQUIRED PER |
| | 13-413.1.ABC.1.1, .1.2 |
| | |
| | 4) NOTE: PLEASE SEE NO LIGHTING CONTROLS ARE SHOWN PER |
| | 13-415.1.ABC.1.1, .1.2. |
| | PLEASE BE SURE TO SEE FBC CHAPTER 10 FOR USE OF ANY |
| | OCCUPANCY SENSORS ON EGRESS AREA LIGHTING AND SEE |
| | NFPA-101 7.8.1.2.2, FBC 1006.1.2 |
| | |
| | 5) NOTE: PLEASE PROVIDE MORE INFORMATION ON HOUSE PANEL |
| | WHICH IS NOTED AS BEING REPLACED. |
| | RISER HAS NOTE WHICH MENTIONS TO SEE NOTE #1, HOWEVER |
| | COULD NOT LOCATE ANY NOTE #1 ON THAT SAME SHEET FOR |
| | INFORMATION ON PANEL CHANGE OUT. |
| | |
| | 6) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ADA |
| | COMPLIANCE FOR HORN AND STROBE DEVICES PER FBC |
| | 11-4.28.1,.2 AND .3(4) |
| | |
| | *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |