| 2007-11-06 09:35:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) SHOW COMPLYANCE WITH 2004 FBC/M 502.3 |
| | BATTERY-CHARGING AREAS. VENTILATION SHALL BE PROVIDED |
| | IN AN APPROVED MANNER IN BATTERY-CHARGING AREAS TO |
| | PREVENT A DANGEROUS ACCUMULATION OF FLAMMABLE GASES. |
| | 502.4 STATIONARY LEAD-ACID BATTERY SYSTEMS. VENTILATION |
| | SHALL BE PROVIDED FOR STATIONARY LEAD-ACID BATTERY |
| | SYSTEMS IN ACCORDANCE WITH THIS CHAPTER AND SECTION |
| | 502.4.1 OR 502.4.2. |
| | 502.4.1 HYDROGEN LIMIT. THE VENTILATION SYSTEM |
| | SHALL BE DESIGNED TO LIMIT THE MAXIMUM CONCENTRATION OF |
| | HYDROGEN TO 1.0 PERCENT OF THE TOTAL VOLUME OF THE |
| | ROOM. |
| | 502.4.2 VENTILATION RATE. CONTINUOUS VENTILATION |
| | SHALL BE PROVIDED AT A RATE OF NOT LESS THAN 1 CUBIC |
| | FOOT PER MINUTE PER SQUARE FOOT (CFM/FT 2 ) [0.00508 M |
| | 3 /(S.M 2)] OF FLOOR AREA OF THE ROOM. |
| | 502.5 VALVE-REGULATED LEAD-ACID BATTERIES. |
| | VALVE-REGULATED LEAD-ACID BATTERY SYSTEMS AS REGULATED |
| | BY THE FLORIDA FIRE PREVENTION CODE , SHALL BE PROVIDED |
| | WITH VENTILATION IN ACCORDANCE WITH SECTION 502.5.1 OR |
| | 502.5.2 FOR ROOMS AND IN ACCORDANCE WITH SECTION |
| | 502.5.3 OR 502.5.4 FOR CABINETS. |
| | |