2007-11-05 16:40:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PROVED COMBUSTION AIR CALCULATIONS FOR GAS TANK-LESS
 WATER HEATER ON MECHANICAL PLAN, SEE FBC/R G2407.1, AND
 PROVIDE COMBUSTION AIR IF REQUIRED.
  
 2) PROVIDE MAKEUP AIR FOR GAS TANK-LESS WATER HEATER,
 SEE FBC/R G2407.4.
  
 3) SHOW ON MECHANICAL PLAN WERE THE CLOTHES DRYER VENT
 WILL DISCHARGE TO. CLOTHES DRYER VENT MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, SEE FBC/R R303.4.2.
  
 4) SEE MECHANICAL PLAN, THE SUPPLY AIR GRILL AND DUCT
 IN LAUNDRY / STORAGE ROOM IS NOT LEGIBLE, SEE WPB AMEND
 106.1.3. PLEASE CORRECT.
  
 5) SIZE ALL RETURN AIR DUCTS AND GRILLS ON MECHANICAL
 PLAN, SEE WPB AMEND. 106.3.5.4.
  
 6) MECH. PLAN SHOWS A RETURN AIR GRILL IN THE BATH
 ROOM, RETURN AIR MAY NOT BE TAKEN FROM A BATHROOM, SEE
 FBC/R M1602.2 (5). PLEASE CORRECT.
  
 7) SHOW A BATHROOM EXHAUST FAN IN GUEST BATH ON
 MECHANICAL PLAN, SEE FBC/R R303.3 EXCEPT.
  
 8) PLANS SHOW TWO A/C CONDENSER PADS, PLEASE CORRECT OR
 EXPLAIN.
  
 9) SHOW ON MECH. PLAN H.V.A.C. SPECIFICATIONS THE
 HEATER KW, SEE WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]