| 2007-11-05 16:40:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PROVED COMBUSTION AIR CALCULATIONS FOR GAS TANK-LESS |
| | WATER HEATER ON MECHANICAL PLAN, SEE FBC/R G2407.1, AND |
| | PROVIDE COMBUSTION AIR IF REQUIRED. |
| | |
| | 2) PROVIDE MAKEUP AIR FOR GAS TANK-LESS WATER HEATER, |
| | SEE FBC/R G2407.4. |
| | |
| | 3) SHOW ON MECHANICAL PLAN WERE THE CLOTHES DRYER VENT |
| | WILL DISCHARGE TO. CLOTHES DRYER VENT MAY NOT DISCHARGE |
| | NEAR THE A/C CONDENSER UNIT, SEE FBC/R R303.4.2. |
| | |
| | 4) SEE MECHANICAL PLAN, THE SUPPLY AIR GRILL AND DUCT |
| | IN LAUNDRY / STORAGE ROOM IS NOT LEGIBLE, SEE WPB AMEND |
| | 106.1.3. PLEASE CORRECT. |
| | |
| | 5) SIZE ALL RETURN AIR DUCTS AND GRILLS ON MECHANICAL |
| | PLAN, SEE WPB AMEND. 106.3.5.4. |
| | |
| | 6) MECH. PLAN SHOWS A RETURN AIR GRILL IN THE BATH |
| | ROOM, RETURN AIR MAY NOT BE TAKEN FROM A BATHROOM, SEE |
| | FBC/R M1602.2 (5). PLEASE CORRECT. |
| | |
| | 7) SHOW A BATHROOM EXHAUST FAN IN GUEST BATH ON |
| | MECHANICAL PLAN, SEE FBC/R R303.3 EXCEPT. |
| | |
| | 8) PLANS SHOW TWO A/C CONDENSER PADS, PLEASE CORRECT OR |
| | EXPLAIN. |
| | |
| | 9) SHOW ON MECH. PLAN H.V.A.C. SPECIFICATIONS THE |
| | HEATER KW, SEE WPB AMEND. 106.3.5.4 (10). |
| | |