Plan Review Notes
Plan Review Notes For Permit 07100862
Permit Number 07100862
Review Stop E
Sequence Number 1
Notes
Date Text
2007-11-05 10:33:48 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.INDICATE THE PANEL LOCATION
  
 2} THE MAIN LUG ONLY PANEL SHOWN ON THE RISER DIAGRAM
 DOES NOT COMPLY WITH 225.31FOR THE REQUIRED
 DISCONNECTING MEANS. ALSO SEE 225.32 FOR LOCATION.
  
 3} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66.
 INDICATE SAME ON THE RISER DIAGRAM.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). NO RECEPTACLE IS SHOWN ON
 THE PLAN.
  
 5} ONLY ONE SMALL APPLIANCE CIRCUIT IS IN THE LOAD
 CALCS. PER 210.11(C)(1) TWO ARE REQUIRED. ALTHOUGH NO
 WORK IS BEING DONE IN THE MAIN HOUSE, TWO ARE REQUIRED
 IN THE GUEST HOUSE.
  
 6} THE SMOKE ALARMSHOWN IN THE GUEST BEDROOM IS
 INCORRECTLY PLACED, BOTH ARE INSIDE THE ROOM, ONE IS
 REQUIRED TO BE IMMEDIATLY OUTSIDE.R313.1.2 RES FBC.
  
 7} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14 A/C UNITS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  