| Plan Review Notes For Permit 07100861 |
| Permit Number |
07100861 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-02 10:43:31 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS, | | | CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION | | | FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT. | | | | | | 2} ALL PLANS SUBMITTED FOR REVIEW MUST HAVE A CITY | | | PLACE STAMP. 106.1.3 | | | | | | 3} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE | | | LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED | | | UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC. THERE | | | ARE SEVERAL SHEETS SUBMITTED WITH THE APPLICATION, NONE | | | OF WHICH SEEM TO BE RELEVANT TO THE DESCRIPTION ON THE | | | APPLICATION. | | | | | | 4} THE PERSON SEALING THE DOCUMENT MUST ALSO PRINT HIS | | | NAME IN THE TITLE BLOCK PER 61G1-16.004 FAC. | | | | | | 5} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE | | | OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8). | | | | | | PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 | | | FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|