| 2008-01-18 13:17:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | **PREVIOUS REVIEW COMMENTS** |
| | |
| | 1. **OK** COMMENT ADDRESSED HOWEVER SEE NEW COMMENTS |
| | ON THE RESUBMITTED SANITARY RISER. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | 3. **OK** COMMENT ADDRESSED. |
| | |
| | 4. **OK** COMMENT ADDRESSED. |
| | |
| | 5. **RESPONSE NOTED, HOWEVER SEE NOTE: FOR COMMENT |
| | #5.** |
| | SHEET A-1 EXISTING A-1 EXISTING OR PROPOSED FLOOR PLAN |
| | DOES NOT INDICATE A DRINKING FOUNTAIN. PER FBC PLUMBING |
| | TABLE *03.1(2) BUSSINESS, A DRINKING FOUNTAIN IS |
| | REQUIRED AND SHALL BE ACCESSIBLE PER THE FOLLOWING, |
| | ALSO PLEASE INDICATE IF THE BATHROOMS ARE ACCESSIBLE. |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| | OF THE FRONT OF FOUNTAIN. |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | **NOTE: THE RESUBMITTED PLANS ARE INDICATING THE |
| | REQUIRED DRINKING FOUNTAIN, HOWEVER THE REQUIRED |
| | ELEVATION DETAIL WITH THE ABOVE REQUIREMENTS FOR THE |
| | DRINKING FOUNTAIN WERE NOT ON THE RESUBMITTED PLANS. |
| | PLEASE COMPLY ON THE RESUBMITTAL. |
| | |
| | 6. **RESPONSE NOTED, HOWEVER SEE NOTE: FOR COMMENT |
| | #6.** |
| | THERE WERE NO ENERGY CALCULATIONS SUBMITTED FOR THE |
| | NEW PROPOSED 50 GAL. WATER HEATER PER CHAPTER 13 ENERGY |
| | EFFICIENCY SECTION 13-101.0 GENERAL. THIS CODE IS A |
| | STATEWIDE UNIFORM CODE AND SHALL NOT BE MADE MORE |
| | STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE CODE |
| | PROVIDES FOR A UNIFORM STANDARD OF ENERGY EFFICIENCY |
| | BY, AT A MINIMUM, SETTING FORTH MINIMUM REQUIREMENTS |
| | FOR EXTERIOR ENVELOPES, LIGHTING, ELECTRICAL |
| | DISTRIBUTION, AND SELECTION OF HEATING, LIGHTING, |
| | VENTILATION, AIR CONDITIONING AND SERVICE WATER HEATING |
| | SYSTEMS. IT SHALL APPLY TO ALL NEW BUILDINGS, TO |
| | ADDITIONS TO EXISTING BUILDINGS AND MANUFACTURED HOMES, |
| | TO RENOVATIONS TO EXISTING BUILDINGS, BOTH PUBLIC AND |
| | PRIVATE, WITH CERTAIN EXCEPTIONS, TO CHANGES OF |
| | OCCUPANCY TYPE, TO THE SITE-INSTALLED COMPONENTS AND |
| | FEATURES OF A MANUFACTURED HOMES AT THEIR FIRST SET-UP, |
| | AND TO THE INSTALLATION OR REPLACEMENT OF BUILDING |
| | SYSTEMS AND COMPONENTS WITH NEW PRODUCTS FOR WHICH |
| | THERMAL EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW |
| | BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND |
| | IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF |
| | INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH |
| | SUBCHAPTER 13-4 OR 13-6 OF THIS CODE. |
| | |
| | **NOTE: THE ENERGY CALCULATIONS FOR THE WATER HEATER |
| | WERE NOT IN THE RESUBMITAL. |
| | |
| | 7. **RESPONSE NOTED** |
| | PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT |
| | IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE - |
| | 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY., BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS TO THE SANITARY |
| | ISOMETRIC RISER DIAGRAM DUE TO DESIGN CHANGES FROM THE |
| | PREVIOUS PLAN REVIEW** |
| | |
| | 8. SHEET A-4 SANITARY RISER DIAGRAM: PLEASE SIZE ALL |
| | WASTE, VENTS, AND TRAPS. PER CHAPTER 1 CITY AMENDMENTS, |
| | SECTION *106.3.5.1.3 PLUMBING, FBC PLUMBING SECTIONS |
| | *701.1 SCOPE AND 901.1 SCOPE. |
| | |
| | 9. SHEET A-4 SANITARY RISER DIAGRAM: A WATER-SEAL TRAP |
| | IS REQUIRED FOR THE TUB. PER FBC PLUMBING SECTION |
| | *1002.1 FIXTURE TRAP. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |