 BUILDING PLAN REVIEW
 PERMIT: 07100843
 ADD: 10130 NORTHLAKE BLVD
 CONT: DOUGLAS M PISARSKI INC.
 TEL: (561)662-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST - 1/28/08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) OK
  
 **NOTE: SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS
 WITH INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A
 SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN
 70 INCHES ABOVE THE DRAIN INLET FBC 1210.3. THE
 RESPONSE SHEET INDICATES 4 FEET.**
 2)THE NEW SHOWER SHALL BE IN COMPLIANCE WITH FBC
 1210.3. THE WALLS SHALL BE FINISH WITH A SMOOTH
 NONABSORBENT SURFACE. PAINT ALONE ON DRYWALL OR DUROCK
 IS NOT CONSIDERED NONABSORBENT. WALL WITHIN 2 FEET OF
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD
 NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE THE
 FINISH FLOOR. FBC1210.2. NOTE: EPOXY PAINT ON DRYWALL
 IS NOT CONSIDERED A HARD SURFACE.
 3)OK
 4) OK
 **THE LEVEL OF ALTERATION SHALL BE INDICATED ON THE
 PLANS.**
 5)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
 6)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]