| 2007-11-13 11:10:55 | |
| | |
| | |
| | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET A-3 AND A-4, UNLESS |
| | OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 |
| | NEC UNLESS OTHERWISE NOTED. |
| | |
| | 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| | FBC AS AMENDED. THER ARE REFERENCES TO OUTDATED CODES |
| | THROUGHOUT THE PLANS. |
| | |
| | 2} THE ARCHITECTS SEAL MUST BE DATED PER 61G1-16.004(4) |
| | FAC. ONLY ONE SET OF PLANS ARE SEALED. TWO SETS OF ALL |
| | DOCUMENTS MUST BE SUBMITTED FOR REVIEW PER 106.1 FBC AS |
| | AMENDED. |
| | |
| | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | THE DISCONNECT LOCATION HAS BEEN OMITTED. |
| | |
| | 4} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| | ARTICLE. NOTE SAME ON THE PLANS ELECTRICAL SHEETS. |
| | |
| | 5} SHEET A-4 INDICATES THE METER BEING FED FROM A |
| | GUTTER.PROVIDE A SITE PLAN INDICATING THE LOCATION OF |
| | ALL SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE |
| | 230 CAN BE REVIEWED. PROVIDE CONDUIT AND CONDUCTOR SIZE |
| | AND TYPE FOR THE SERVICE EQUIPMENT FROM THE GUTTER. IT |
| | CANNOT BE DETERMINED IF THERE IS A DISCONNECTING MEANS |
| | AHEAD OF THE METER SHOWN OR IF THIS IS A SEPERATE |
| | SERVICE. THE EQUIPMENT GROUNDING CONDUCTOR RAN TO THE |
| | DISCONNECT SHOULD BE REMOVED IF IT IS DETERMINED THAT |
| | THE DISCONNECT SHOWN IS THE FIRST MEANS. SEE |
| | 250.24(A)(5), 2005 NEC. |
| | |
| | 6} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 7} THE LOAD CALCULATION GIVEN IS FOR A RESIDENTIAL UNIT |
| | AS EVIDENCED WITH THE SMALL APPLIANCE CIRCUITS AND |
| | TAKING A 65% DEMAND ON THE HEAT, BOTH ARE SPECIFIC |
| | CALCULATIONS FOR DWELLINGS. SUBMIT CALCULATIONS PER |
| | 215.2(A)(1), 125% OF CONTINUOUS LOADS,220.12, 220.14, |
| | 220.16 AND 220 PART III. |
| | |
| | 8}THE PANEL SCHEDULE CIRCUIT #2,4 INDICATES A DRYER, |
| | CIRCUIT #8 INDICATES A WASHER. SHEET A-3 SHOWS A |
| | WASHER/DRYER COMBO, WITH NO CIRCUIT NUMBERS. CORRELATE |
| | SAME. |
| | |
| | 9} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS, |
| | CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION |
| | FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT. 106.1.2. |
| | FBC AS AMENDED. |
| | |
| | 10} THE X-RAY EQUIPMENT MUST BE INCLUDED IN THE LOAD |
| | CALCULATION PER 220.14(A). SEE ARTICLE 660, 2005 NEC. |
| | |
| | |
| | 11} PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT |
| | OLD SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO |
| | THE COMMENTS MADE IN THIS REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |