 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A-3 AND A-4, UNLESS
 OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2005
 NEC UNLESS OTHERWISE NOTED.
  
 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED. THER ARE REFERENCES TO OUTDATED CODES
 THROUGHOUT THE PLANS.
  
 2} THE ARCHITECTS SEAL MUST BE DATED PER 61G1-16.004(4)
 FAC. ONLY ONE SET OF PLANS ARE SEALED. TWO SETS OF ALL
 DOCUMENTS MUST BE SUBMITTED FOR REVIEW PER 106.1 FBC AS
 AMENDED.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 THE DISCONNECT LOCATION HAS BEEN OMITTED.
  
 4} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. NOTE SAME ON THE PLANS ELECTRICAL SHEETS.
  
 5} SHEET A-4 INDICATES THE METER BEING FED FROM A
 GUTTER.PROVIDE A SITE PLAN INDICATING THE LOCATION OF
 ALL SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE
 230 CAN BE REVIEWED. PROVIDE CONDUIT AND CONDUCTOR SIZE
 AND TYPE FOR THE SERVICE EQUIPMENT FROM THE GUTTER. IT
 CANNOT BE DETERMINED IF THERE IS A DISCONNECTING MEANS
 AHEAD OF THE METER SHOWN OR IF THIS IS A SEPERATE
 SERVICE. THE EQUIPMENT GROUNDING CONDUCTOR RAN TO THE
 DISCONNECT SHOULD BE REMOVED IF IT IS DETERMINED THAT
 THE DISCONNECT SHOWN IS THE FIRST MEANS. SEE
 250.24(A)(5), 2005 NEC.
  
 6} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 7} THE LOAD CALCULATION GIVEN IS FOR A RESIDENTIAL UNIT
 AS EVIDENCED WITH THE SMALL APPLIANCE CIRCUITS AND
 TAKING A 65% DEMAND ON THE HEAT, BOTH ARE SPECIFIC
 CALCULATIONS FOR DWELLINGS. SUBMIT CALCULATIONS PER
 215.2(A)(1), 125% OF CONTINUOUS LOADS,220.12, 220.14,
 220.16 AND 220 PART III.
  
 8}THE PANEL SCHEDULE CIRCUIT #2,4 INDICATES A DRYER,
 CIRCUIT #8 INDICATES A WASHER. SHEET A-3 SHOWS A
 WASHER/DRYER COMBO, WITH NO CIRCUIT NUMBERS. CORRELATE
 SAME.
  
 9} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT. 106.1.2.
 FBC AS AMENDED.
  
 10} THE X-RAY EQUIPMENT MUST BE INCLUDED IN THE LOAD
 CALCULATION PER 220.14(A). SEE ARTICLE 660, 2005 NEC.
  
  
 11} PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT
 OLD SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER