2008-06-11 08:24:26******PROVISO******
 A} PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN
 THE INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
  
 B} REVISION WILL BE REQUIRED ON THE FLOOR PLAN FOR THE
 BAR SINK LOCATION BEING INDICATED ON PLUMBING RISER
 "B". PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C} CLEANOUTS AT THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER SHALL BE TWO-WAY CLEANOUTS. PER FBC-2004
 PLUMBING SECTION 708.3.5.
  
 D} CLEANOUT REQUIRED AT THE BASE OF THE 3 INCH STACK
 FOR PLUMBING RISER "B". PER FBC-2004 PLUMBING SECTION
 708.3.4.
  