Plan Review Notes
Plan Review Notes For Permit 07100792
Permit Number 07100792
Review Stop P
Sequence Number 2
Notes
Date Text
2008-02-25 11:19:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 1. SHEET 3 PLUMBING RISER "A": THE WASHING MACHINE
 WASTE STACK NEEDS TO BE 3". PER FBC PLUMBING SECTION,
 *406.3 WASTE CONNECTION.
  
 2. SHEET 3 PLUMBING RISER "A": THE 1ST FLOOR NEW BATH
 WATER CLOSET AND THE 2ND FLOOR MASTER BATH NEW TUB ARE
 NOT VENTED. PER FBC PLUMBING SECTION *901.2.1 VENTING
 REQUIRED.
  
 3.SHEET 3 PLUMBING RISER "A": ONLY FIXTURES WITHIN TWO
 BATHROOM GROUPS LOCATED ON THE SAME FLOOR ARE PERMITTED
 TO BE VENTED BY THE VERTICAL WET VENT. THE DOUBLE BOWL
 KITCHEN SINK IS NOT ALLOWED TO DRAIN INTO THIS. PER FBC
 PLUMBING SECTION 909.1.1 VERTICAL WET VENT.
 THE KITCHEN SINK CAN USE AN AIR ADMITTANCE VALVE. PER
 FBC PLUMBING SECTION *917.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]