2008-02-25 12:00:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600C-04R,
 SEE 2004 FBC 13-600.3.C (12-8-06 REVISION).
  
 2) WHEN SUBMITTING REVISED ENERGY CALCULATIONS THEY
 NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) PROVIDE FOR RETURN AIR TO THE MASTER BEDROOM SUITE,
 SEE 2004 FBC/R M1604.2.
  
 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  