2008-02-26 09:42:082004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 3) THE ENERGY CALCULATION FORM IS OUTDATED. THE CURRENT
 FORM IS 600C-04. THE FORM IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER/AGENT. SEE FBC 11-600.
  
 4) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, FLOOR
 FRAMING PLAN AND SHOP DRAWINGS FOR THE HAMBRO FLOOR
 SYSTEM. FBC 106.1.2* CITY AMENDMENTS
  
 5) SHOP DRAWINGS WILL BE REQUIRED FOR THE GUARD RAILS
 AT THE BALCONY, SHOWING COMPLIANCE WITH R312. FBC
 106.1.2* CITY AMENDMENTS
  
 6) THE WINDLOAD SCHEDULE ON SHEET 2 DOES NOT SPECIFY
 THE PRESSURES FOR ROOF ZONE 3. PLEASE REVISE. SEE FBC
 TABLE R301.2(2).
  
 7) THE ROOF ZONE DIAGRAM ON SHEET 2 DOES NOT INDICATE
 ROOF ZONE 3 AT THE CORNERS. PLEASE CORRECT. SEE FIGURE
 R301.2 (8).
  
 8) REVISE THE ROOF SHEATHING NAILING SCHEDULE ON SHEET
 2 TO COMPLY WITH R803.2.3.1 SHEATHING FASTENINGS. WOOD
 STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO ROOF
 FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON CENTER
 AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING
 MINIMUM DIMENSIONS:
 1.0.113-INCH NOMINAL SHANK DIAMETER
 2.RING DIAMETER OF 0.012 OVER SHANK DIAMETER 3.
 16 TO 20 RINGS PER INCH
 4.0.280 INCH FULL ROUND HEAD DIAMETER
 5.2-INCH NAIL LENGTH
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G <
 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE
 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR
 GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE
 R803.2.3.1 .
  
 9) THE STATEMENT ON SHEET 2 THAT RING SHANK NAILS ARE
 NOT REQUIRED WHEN MEAN ROOF HEIGHT IS LESS THAN 25 FEET
 IS INCORRECT. PLEASE REVISE. SEE R 803.2.1.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE ROOF ACCESS HATCH
 AND THE SKYLITE SHOWN ON THE ROOF FRAMING PLAN ON SHEET
 3. FAC RULE 9B-72
  
 11) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE GAF
 MODIFIED ROOF SYSTEM IS INCOMPLETE. THE SHEETS WITH THE
 APPROVED ASSEMBLY AND LIMITATIONS ARE MISSING. THE
 APPROVED ASSEMBLY, THE FASTENING OPTION, THE DESIGN
 PRESSURE AND RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING THAT WILL BE USED ARE REQUIRED TO BE
 SPECIFIED.
  
 12)PRODUCT APPROVAL FL4904 FOR THE MASONITE
 INTERNATIONAL EXTERIOR DOORS IS OK FOR THE SINGLE
 INSWING DOOR. HOWEVER, THE DESIGN PRESSURES ARE TOO LOW
 FOR THE NON-IMPACT RATED GLAZED DOUBLE DOORS. WHEN
 MULTIPLE PRODUCT APPROVALS FOR THE SAME ITEMS ARE
 SUBMITTED IT IS HELPFUL IF THE SPECIFIC ITEM TO WHICH
 IT APPLIES IS NOTED THE PRODUCT APPROVAL. FAC RULE
 9B-72
  
 13) THE DRAWINGS ATTACHED TO THE COVERSHEET FOR THE PGT
 SINGLE HUNG WINDOWS ARE THE WRONG ONES AND ARE EXPIRED.
 SEE FL 2939-R10. FAC RULE 9B-72
  
 14) DUE TO THE REVISIONS TO THE PLANS, THE PRODUCT
 APPROVALS FOR THE ROOF TILE NO LONGER APPLY. PLEASE
 REMOVE THEM FROM THE SUBMITTALS.
  
 15) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 ANCHOR TYPE, ANCHOR SPACING, EDGE DISTANCE, ETC. FBC
 301.2.1.2SEE SAMPLE INSTALLATION SCHEDULE ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]