Plan Review Notes
Plan Review Notes For Permit 07100792
Permit Number 07100792
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-30 08:54:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET 4-4 , UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} INDICATE THE SERVICE CONDUCTOR SIZE AND NUMBER FOR
 THE FEED TO THE DISCONNECT FROM THE METER.310.16,
 250.2. 2005 NEC.
  
 2} THE PANEL SCHEDULE/LOAD CALCULATION ONLY LISTS ONE
 SMALL APPLIANCE CIRCUIT. A MINIMUM OF TWO ARE REQUIRED
 PER 210.11(C)(1).
  
 3} THERE IS A MECHANICAL PERMIT APPLIED FOR BUT NO
 MECHANICAL PLANS SUBMITTED. INDICATE IF ANY OF THE
 MECHANICAL WIRING IS PART OF THIS PERMIT. THE
 DISCONNECTS AT THE CONDENSING UNIT DO NOT COMPLY WITH
 THE CLEARANCE REQUIREMENTS OF 110.26.AHU #1 AND #2 IN
 THE CLOTHES CLOSETS MAY BE IN VIOLATION OF 422.17 AND
 240.24(D) IF OVERCURRENT PROTECTION IS PRESENT IN THE
 CLOSET.
  
 4} THE TITLE BLOCK ON THIS SHEET IS INDISCERNIBLE.
 106.1.1 FBC AS AMENDED.
  
 5} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]